Rne configuration, Rne confi guration screens, Vcm-x / rne operator interfaces technical guide – Orion System VCM-X/RNE Operator Interfaces User Manual
Page 35

VCM-X / RNE Operator Interfaces Technical Guide
RNE CONFIGURATION
35
Confi guration Screen #40 - Broadcast OA Temp
RNE Cnfg ID 101
Broadcast Outdoor
Temperature: NO
[0=NO 1=YES]
The RNE can broadcast its Outdoor Air Temperature Reading to other
HVAC units if they are not equipped with their own Outdoor Air Tem-
perature sensors. A network communications device is needed in order
for this feature to operate. Enter
<1>
for YES - Broadcast Outdoor
Temperature. Enter
<0>
for NO. Default is NO.
Confi guration Screen #41 - Broadcast OA Humidity
RNE Cnfg ID 101
Broadcast Outdoor
Humidity: NO
[0=NO 1=YES]
The RNE can broadcast its Outdoor Air Humidity reading to other HVAC
units if they are not equipped with their own Outdoor Air Humidity
sensors. A network communications device is required in order for this
feature to operate. Enter
<1>
for YES - Broadcast Outdoor Humidity.
Enter
<0>
for NO. Default is NO.
Confi guration Screen #42 - Broadcast Supply
Temperature
RNE Cnfg ID 101
Broadcast Supply
Temperature: YES
[0=NO 1=YES]
This broadcast sends the RNE’s Supply Air Temperature to all Control-
lers on its local loop. This broadcast needs to be confi gured on a VAV
or Zoning System using the RNE with Orion VAV/Zone Controllers. A
network communications device is required in order for this feature to
operate. Enter
<1>
for YES or
<0>
to NO. Default is NO.
Confi guration Screen #43 - Broadcast Status
Fan & Heat
RNE Cnfg ID 101
Broadcast Status
Fan & Heat: NO
[0=NO 1=YES]
This broadcast sends the RNE’s Supply Fan and Heating Status to all
Controllers on its local loop. This broadcast needs to be confi gured on
a VAV or Zoning System using the RNE with Orion VAV/Zone Con-
trollers. A network communications device is required in order for this
feature to operate. Enter
<1>
for YES or
<0>
for NO. Default is NO.
Confi guration Screen #44 - Broadcast Internal
Time Clock
RNE Cnfg ID 101
Broadcast Internal
Time Clock: NO
[0=NO 1=YES]
This broadcast sends the time from the RNE’s Internal Time Clock to all
Controllers on its local loop. This broadcast needs to be confi gured on a
VAV or Zoning System using the RNE with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to
operate, but can also be used to synchronize all Controllers on the local
loop. Enter
<1>
for YES or
<0>
for NO. Default is NO.
Confi guration Screen #45 - Broadcast Internal
Schedule
RNE Cnfg ID 101
Broadcast Internal
Schedule: NO
[0=NO 1=YES]
This is always required when you have VAV/Zone Controllers connected
to this RNE Controller. This will broadcast the Occupied and Unoccupied
Condition of the RNE Controller to all VAV/Zone Controllers on the
local loop. Enter
<1>
for YES or
<0>
for NO. Default is NO.
RNE Confi guration Screens