VCM-X / RNE Operator Interfaces Technical Guide

VCM-X / RNE SETPOINTS

41

Setpoint Screen #8 - Stage Control Window

VCM-X / RNE Spts

Stage Control Window

Cooling.........: 5ºF
Heating.........: 5ºF

When the VCM-X or RNE is in Cooling Mode, if the Supply Air
Temperature drops below the Active Supply Air Temperature Setpoint
minus the Cooling Stage Control Window value, a Cooling Stage will
be deactivated after its Minimum Run Time. In the Heating Mode, if the
Supply Air Temperature rises above the Active Supply Air Temperature
Setpoint plus the Heating Stage Control Window value, a Heating stage
will be deactivated after its Minimum Run Time. This staging window
is also used for the coil temperature during Dehumidifi cation Mode.

Description

Minimum

Default

Maximum

Stage Control Window Cooling

5ºF

5ºF

30ºF

Stage Control Window Heating

5ºF

5ºF

30ºF

Setpoint Screen #9 - Outdoor Air Lockouts

VCM-X / RNE Spts

Outdoor Air Lockouts

Cooling......: 50ºF
Heating......: 70ºF

The VCM-X or RNE will Lockout Mechanical Heating or Cooling when
the Outdoor Air (OA) Temperature is above or below these Setpoints.

On Air to Air Heat Pump units, Compressor Cooling and Heating can
only operate if the OA Temperature is above the Outdoor Air Cooling
Lockouts. If using the VCM-X WSHP (Water Source Heat Pump) Con-
troller, the OA Cooling Lockout is ignored. Since Emergency Heat can
only be used below the Compressor Lockouts, Emergency Heat is there-
fore not available on WSHP units using the VCM-X WSHP Controller.

Description

Minimum

Default

Maximum

OA Lockouts Cooling

0ºF

50ºF

100ºF

OA Lockouts Heating

50ºF

70ºF

150ºF

Setpoint Screen #10 - Cutoff Temperature

VCM-X / RNE Spts

Cutoff Temperatures

Lo SAT.......: 40ºF
Hi SAT.......: 170ºF

The VCM-X or RNE will temporarily disable Heating or Cooling if
while in Heating or Cooling Mode the Supply Air Temperature rises
above the High SAT Cutoff Temperature Setpoint or falls below the Low

VCM-X / RNE Setpoint Screens

SAT Cutoff Temperature Setpoint. See the VCM-X Controller Technical
Guide
, VCM-X Modular E-BUS Controller Technical Guide, or RNE
Controller Technical Guide
for detailed information on the Low and
High Supply Air Temperature Cutoff sequence of operation.

Description

Minimum

Default

Maximum

Lo SAT Cutoff

0ºF

40ºF

250ºF

Hi SAT Cutoff

0ºF

170ºF

250ºF

Setpoint Screen #11 - Minimum Supply Fan

VFD Speed For Heating

VCM-X / RNE Spts

Minimum Supply

Fan VFD Speed

For Heating..: 30%

If the Supply Fan VFD Signal falls below the Minimum Supply Fan
VFD Speed For Heating Setpoint, Heating will be disabled.

Description

Minimum

Default

Maximum

Min Supply Fan VFD

Speed For Heating

0%

30%

100%

Setpoint Screen #12 - Morning Warm Up Temp

VCM-X / RNE Spts

Morning WarmUp

Target Temp: 72º F

Max Length.: 60 Min

When the VCM-X or RNE is confi gured for VAV operation and the
controller enters the Occupied Mode, the VCM-X or RNE looks at the
Return Air Temperature to determine if the unit should initiate Morning
Warm-up Mode. If the Return Air Temperature is below the Morning
Warm-up Target Temperature and the Max Length is greater than “0,”
the VCM-X or RNE will initiate Heating. This is considered Morning
Warm-up and will run until the Return Air Temperature rises above the
Morning Warm-up Target Temperature or until the Max Length Setpoint
time expires.

Description

Minimum

Default

Maximum

Morning Warm Up

Target Temp

50ºF

72ºF

90ºF

Morning Warm Up

Max Length

0 Min

60 Min

240 Min