Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interfaces technical guide 49 – Orion System VCM-X/RNE Operator Interfaces User Manual
Page 49: Status

VCM-X / RNE STATUS
VCM-X / RNE Operator Interfaces Technical Guide
49
VCM-X / RNE Status Screens
Status
The VCM-X / RNE Controller Status Screens are accessed by pressing
the
button on either the System Manager or the Modular
Service Tool. Following are the available status screens and a descrip-
tion of their functions:
Status Screen 1 - Mode
VCM-X / RNE v1.00
Occupied Mode
Vent Mode
02/15/10 05:00 PM
Line 2 Displays one of the following:
Unoccupied Mode Remote FRC Occupied
Occupied
Mode Override
Mode
Holiday
Mode
Zone
Demand!
Forced Schedule Mode OUTPUT FORCE MODE!
SUPPLY AIR CUTOFF! High CO2 Level Mode!
Line 3
If you selected Supply Air as the controlling sensor,
this line will display:
Supply Air Control
If you select Space Temp or Return Air Control, the
display will show one of the following:
Off Mode Dehumid. Mode
Defrost Mode
Vent Mode Cool Dehumid. Mode
Cool Mode Heat Dehumid. Mode
Heat Mode Warm Up Mode
Line 4
Displays one of the following:
MM/DD/YY HH:MM XX (XX = AM or PM)
Fan Starting Delay and then time will display
xx Left in WarmUp (Number of Minutes Left)
Status Screen 2 - Cooling, Heating, Economizer
VCM-X / RNE v1.00
Cooling Enabled
Heating Enabled
Economizer Disabled
Line 2
Displays one of the following:
Cooling
Enabled
Cooling
Disabled
Line 3
Displays one of the following:
Heating
Enabled
Heating
Disabled
Line 4
Displays one of the following:
Economizer Enabled
Economizer
Disabled
Status Screen 3 - Mode Enable Temperature &
Mode Cooling and Heating Setpoints
VCM-X / RNE v1.00
Enable Tmp.: XX.XºF
Cooling Spt: XX.XºF
Heating Spt: XX.XºF
Line 2 Mode Enable Temperature
Can be the Supply Air Temperature, Return Air
Temperature, Outdoor Air Temperature, or Space
Temperature, depending on which one has been
confi gured as the Mode Enable Sensor.
Line 3
Cooling Mode Setpoint
Based on the current Occupied/Unoccupied Mode
of
operation.
Line 4
Heating Mode Setpoint
Based on the current Occupied/Unoccupied Mode
of
operation.
Status Screen 4 - Supply Air Temperature &
Setpoint
VCM-X / RNE v1.00
Supply Air.: XX.XºF
Supply Spt.: XX.XºF
Line 2 Current Supply Air Temperature
The Supply Air Temperature is always required. If a
Supply Air Temperature Sensor is not installed, the VCM-X
/ RNE Controller will not operate correctly and will display
0°F.
Line 3
Current Active Supply Air Setpoint
This is the Supply Air Setpoint for the mode that the
unit is currently operating in. If the Supply Air Reset is
confi gured, this is the calculated setpoint based on the
current Reset Source conditions.