Pump/Remote Dispenser Wiring

03/07/03

4-15

Pulser Wiring Requirements

When installed in a separate DC conduit, 18 AWG wires are required for installation. Although it is
recommended that DC pulser wires be run in a conduit separate from AC wires, they can be
combined in the same conduit with AC wires providing UL-Listed cable with the following
specifications is used:

Conductor:

18 AWG stranded wire. Number of conductors to be determined by pulser

Shield:

Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage

Drain Wire:

Stranded, tinned copper, 20 AWG or larger/or braided shield

Voltage Rating: Maximum operating voltage of 600V
Environmental: Gas- and oil-resistant; suitable for wet or dry locations.

GASBOY can supply Belden 1063A (P/N C09655) which is a UL-Listed, 4-conductor cable that
meets the requirements listed above. NOTE: Belden 1063A is UL-Listed but not CSA listed.