Wiring

Page 5-22 MDE-4340A Series 9800Q Pumps and Dispensers Installation/Operation Manual · January 2006

024294 Wiring Diagram Models 9853Q 380VAC

Notes:

1

All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and
Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine
Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply
with the Canadian Electrical Code.

CAUTION

CAUTION

To avoid damage to the CPU PC board, all unused wires must be individually capped,
and before applying power, you must verify that the RESET COMPLETE and FAST
FLOW wires are not shorted to conduit or chassis.

2

RESET COMPLETE (switch detect) line can supply 170 mA AC maximum for connecting to
fuel management system circuitry.

3

FAST FLOW line can supply 170 mA AC maximum for remote control or monitoring of the
fast flow valve found in the pump.

4

If the CONTROL/PUMP MOTOR FEED line is controlled by a fuel management system
using solid state relays, a resistor assembly must be installed between the Control Feed line
and Feed Neutral to prevent false triggering of the authorization input. The resistor assembly is
10 Watt (P/N C06683).

5

Use the wire size chart (230VAC section) on

page 5-4

when determining the wire size for the

control wiring.

6

If this unit is equipped with a TopKAT option, there will be 10 wires in the junction box. See
the TopKAT Installation Manual for wiring requirements and information.

7

When used with an aboveground tank, the anti-siphon valve mounted on the tank must be
driven from the EXTERNAL VALVE line, have the same operating voltage as the pump
motor, and the current draw must not exceed 1 Amp. If these conditions are not met, it must be
controlled by an external relay driven from the EXTERNAL VALVE line. DO NOT connect
the anti-siphon valve or external relay to the RESET COMPLETE line. DO NOT connect two
or more EXTERNAL VALVE lines together. If more than one pump is drawing from the tank,
separate anti-siphon valves must be installed, or each EXTERNAL VALVE line must operate
an external relay which then operates the valve.