Flowserve Logix MD+ ValveSight User Manual
Page 93

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD-
LGENSF0014-00
© Flowserve Corporation
93
 
 
 
NOTE:  Flowserve does not recommend any action, only lists possible actions that could 
restore the system to normal operation. Qualified maintenance personnel should evaluate 
the possible solutions, all safety procedures and all other applicable factors on a case by 
case basis when determining the best action to take. 
 
Legend 
The legend shows the purpose of the icons. 
Action Buttons 
The Apply button will save changes to the connected device. 
 
The Retrieve button will retrieve the latest information from the device. 
 
 
Warnings and Alarms 
Supply Pressure High
•
Definition: The supply pressure is above the user set warning limit.
•
Implications: Supply pressure that exceeds the maximum rating on the
actuator can become a potential hazard.
•
Possible Solutions: Regulate the supply pressure at the positioner
below the maximum limit recommended for your actuator. Recalibrate 
pressure sensors. Check the pressure sensor board 
connections. Replace pressure sensor board if necessary. 
Supply Pressure Low
•
Definition: The supply pressure is below the user set warning or alarm