ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD-
LGENSF0014-00
© Flowserve Corporation
177
display a Save dialog to save the current HDRL test to a file. The "Save" dialog will display
a default name including the following:
•
Device Tag ID_
•
HDRL_
•
Year
•
Month
•
Day
•
Time
The Start button will clear the existing data and start the test.
CAUTION: During a test the valve will not respond to control signals and movement of the
valve stem will occur.
The Stop button stops data acquisition and the test.
The Print Report button sends the report to the default printer.
NOTE: It is possible to print the report to save to a PDF file. Instructions:
1. Download and install the free version of PDFCreator.