Flowserve Logix MD+ ValveSight User Manual
Page 148

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD-
LGENSF0014-00
© Flowserve Corporation
148
 
 
This area allows for the selection of items to be shown on the graph. All of the data is 
acquired regardless of this setting. Any item can be hidden or shown after the data has 
been downloaded from the positioner. 
 
Monitors 
Test Status indicates the current state of the test. 
Elapsed Time shows how many seconds have passed since the ramp test began. This 
includes time for data acquisition. 
 
Spring Set 
The Spring Set box shows information about the spring forces in the actuator. 
Spring Initial is the pressure required to initially move the valve as the valve is beginning to 
compress the spring. 
Spring Final is the pressure required position the valve at the end of travel where the spring 
is fully compressed. 
Spring Rate is the average force divided by the distance traveled during spring 
compression. 
 
View Ramp Test 
This graph shows the parameters relative to time. 