Position Shutoff
The Position Shutoff page allows you to change the position shutoff limits. Tight Shutoff 
(also called Minimum Position Cutoff or MPC) mode is used to ensure a fully open or fully 
closed position. Under normal operation, the positioner is balancing the pressure in the 
actuator to maintain the position of the valve. When the commanded position moves past a 
position shutoff limit, the positioner will engage all available force to move the valve to a 
fully closed or open position. One side of the actuator will be saturated with full supply 
pressure while the other side will be left with no pressure. The status of this mode is 
displayed on the Dashboard. 
 
Status Area 
The Active Indicator area shows the status of the most relevant active indicator. The color 
of the "LED light" corresponds to the Active Indicator and the first color of the blink code 
sequence on the positioner. Generally green indicates no immediate issues. Yellow 
indicates a developing issue. Red indicates the ability to control may be compromised. A 
detailed list of the indicators is given in the 
Alarm Congfiguraion - Alarm Annunicator
page.
The Command Source field indicates weather the positioner is being controlled by digital or 
an analog (4-20 mA) command source. 
 
 
Upper Position Shutoff Setting 
The "Upper Position Shutoff Setting" box shows the input command signal above which the 
positioner applies full force to open the valve. The default value is 110%. 
 
Lower Position Shutoff Setting 
The "Lower Position Shutoff Setting" box shows the input command signal below which the 
positioner applies full force to close the valve. The default value is 1% 