Flowserve Logix MD+ ValveSight User Manual
Page 128

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD-
LGENSF0014-00
© Flowserve Corporation
128
Action Buttons
The Apply button will save changes to the connected device.
The Retrieve button will retrieve the latest information from the device.
Warnings and Alarms
Position Amplitude
•
Definition: The amplitude of the position signal is above the warning
limit. The positioner is controlling the position of the valve with large
corrections.
•
Possible Solutions: Verify the limits are set at an appropriate level.
Adjust the selectable Gain switch to a lower setting or use the "Hi
Friction" setting. Perform a QUICK-CAL which sets the gains based on
valve response. Check for high friction. If the problem persists replace
the relay.