ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD-
LGENSF0014-00
© Flowserve Corporation
109
NOTE: Flowserve does not recommend any action, only lists possible actions that could
restore the system to normal operation. Qualified maintenance personnel should evaluate
the possible solutions, all safety procedures and all other applicable factors on a case by
case basis when determining the best action to take.
Legend
The legend shows the purpose of the icons.
Action Buttons
The Apply button will save changes to the connected device.
The Retrieve button will retrieve the latest information from the device.
Warnings and Alarms
Position Deviation
•
Definition: The device is not controlling at the set point
•
Implications: The difference between the command and the actual
position has been greater than the user-set limit for longer than a user-
set time.
•
Possible Solutions: Review active alarms and warnings to find root
causes of this alarm. The deviation settings can be changed in the
Valve Health page of the DTM.
Position Alerts
•
Definition: The position has reached or is exceeding a user defined
upper position indicator. This is similar to a limit switch indicator.