Training – Flowserve Logix MD+ ValveSight User Manual
Page 129

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD-
LGENSF0014-00
© Flowserve Corporation
129
 
 
Training
The Training page allows you to view information about the training period. During the 
training period, the positioner records system data and creates histograms of several 
parameters. The histogram data and graphs are displayed in the DTM pages where the 
related alarm limits are set. The training period should be run during normal operation, 
when there are no issues. It should run over a time period that includes normal process 
variations. By default, the training will begin automatically after 24 hours of continuous 
operation and last 90 days (2160 hours). For more recorded system data, see 
Trends
.
 
During Training, the positioner data for the following: 
•
Supply Pressure
•
Deviation
•
Friction
•
Pneumatic Leak
•
Position
•
Position Frequency
•
Position Amplitude
•
Command Frequency
•
Command Amplitude
 
Status Area 
The Active Indicator area shows the status of the most relevant active indicator. The color 
of the "LED light" corresponds to the Active Indicator and the first color of the blink code 
sequence on the positioner. Generally green indicates no immediate issues. Yellow 
indicates a developing issue. Red indicates the ability to control may be compromised. A 
detailed list of the indicators is given in the 
Alarm Congfiguraion - Alarm Annunicator
page.
The Command Source field indicates weather the positioner is being controlled by digital or