Advanced dashboard – Flowserve Logix MD+ ValveSight User Manual
Page 21

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD-
LGENSF0014-00
© Flowserve Corporation
21
 
 
Advanced Dashboard
The Dashboard view is the main diagnostic view of the ValveSight® DTM. Generally, the 
color green signifies a healthy condition, yellow signifies some degradation has taken 
place, and red signifies a problem that needs to be addressed right away. You can identify 
problems right away by observing any red areas on this page. 
 
 
Status Area 
The Active Indicator area shows the status of the most relevant active indicator. The color 
of the "LED light" corresponds to the Active Indicator and the first color of the blink code 
sequence on the positioner. Generally green indicates no immediate issues. Yellow 
indicates a developing issue. Red indicates the ability to control may be compromised. A 
detailed list of the indicators is given in the 
Alarm Congfiguraion - Alarm Annunicator
page.
The Command Source field indicates weather the positioner is being controlled by digital or 
an analog (4-20 mA) command source. 
 
Command and Position 
This area contains a graphical representations of the valve command and position. The 
blue pointer tracks the final command value after adjustments for characterization curves, 
Soft Limits, and Tight Shut Off. The green position bar indicates the current measured 
position of the valve. The smaller pointers show the settings of the travel alert settings 
(these can be changed on the Travel Alerts page located under Alarms/Alerts). Grayed out 