6. Now you might see some errors in registers 0x030C-0x0313 resulting from power-up. These
errors have no significance, only errors increasing during operation are important.
TwinCAT reads out and clears only the error counters in register 0x0300-0x0307, and pressing the
button “Clear CRC” also clears only these counters. The other counters are still accumulating from
power-up until now.
Please note that the error counters are shown as 16 bit values
, i.e., the column called “Reg. 0300”
shows in fact registers 0x0300 (lower 8 bit, right side) and 0x0301 (higher 8 bit, left side).
Press the buttons “Clear CRC” and “Clear Frames” to clear the TwinCAT counters in the lower
right area (Lost frames, Tx/Rx Errors).
Figure 19: Some power-up errors without significance
7. If you want to clear all the error counters, follow these steps for each ESC.
At first, highlight the ESC with the error counters you want to clear. Right-click into the row and
select “Advanced Settings…” from the context menu.
Figure 20: Clear error counters manually in the advanced settings