Table 4-40, Hpi-b daemon log messages, Using hpi-b – Artesyn System Management Interface Based on HPI-B (Centellis CO 31kX-4100-2000-4410) (June 2014) User Manual
Page 77

Using HPI-B
System Management Interface Based on HPI-B (Centellis CO31kX/4100/2000/4410) User’s Guide
77
Once enabled, the HPI-B daemon log files will have the following log messages:
04:14:21.732
xd=0.04 xdi=-484.7 xdp=0.008 u=14.3
04:14:21.733
9a.0/0/af
04:14:26.698
xd=0.00 xdi=-484.6 xdp=-0.008 u=14.7
04:14:26.699
9a.0/0/af
04:14:31.699
xd=0.05 xdi=-484.5 xdp=0.009 u=14.2
04:14:21.733
9a.0/0/af
Following table describes the way to interpret these log messages.
Cooling_FanConsiderFailureEv
ent
“0”
A “1” treats a fan, which had sent a lower
critical event, as broken and would
increase the speed of the remaining fans
accordingly. Default controls the speed
related to measured temperatures only.
Table 4-40 HPI-B daemon Log Messages
Code in log message
Name, Description
sp
Set Point for the control
y
Filtered value of read sensor
u
Calculated speed in %
xd
Difference of sp - y - tolerance
xdi
Integral
Table 4-39 Parameters of Cooling System (continued)
Parameter Name
Default Value
Description