Using hpi-b – Artesyn System Management Interface Based on HPI-B (Centellis CO 31kX-4100-2000-4410) (June 2014) User Manual
Page 76

Using HPI-B
System Management Interface Based on HPI-B (Centellis CO31kX/4100/2000/4410) User’s Guide
76
Cooling_DeactOnUpperNonRecov
erTemp
“1”
Enables the function to power off all
blades and drop fan speed after
receiving upper non recoverable (UNR)
thermal events from two different
resources in the C2000 shelf.
Cooling_FanMinimumLevel
“12|15”
Default fan speed in %.
12 - default value for C2000 shelfs.
15 - default value for the other shelfs.
Cooling_InletOutletLowerTemp
erature
“20”
Lower temperature point for inlet/outlet
control
Cooling_InletOutletUpperTemp
erature
“40”
Upper temperature point
Cooling_InletOutletLowerSetP
oint
“10”
Set point at upper temperature
Cooling_InletOutletUpperSetP
oint
“25”
Set point at lower temperature Range 25
to 15, most effect at 15. Influences the
difference between in- and outlet
temperature.
Cooling_InltOutltMinimumSens
orTemperature
“18”
Below this inlet temperature the
inlet/outlet related control is disabled
Cooling_BoardSetPointOffset
“0”
The temperature difference to the
upper-non-critical Threshold of a blade.
E. g. threshold at 85, a 5 would result in
holding the temperature at 80. Allowed
range is 0 to 5
Cooling_BoardConsiderHystere
sis
“0”
“1” subtracts a hysteresis from the set
point
Cooling_BoardMinNumControlle
d
“10”
Minimum number of sensors to be
polled after a temperature event
Cooling_BoardMaxNumControlle
d
“10”
Maximum number of sensors to be
polled Both should not be changed
Table 4-39 Parameters of Cooling System (continued)
Parameter Name
Default Value
Description