Using HPI-B

System Management Interface Based on HPI-B (Centellis CO31kX/4100/2000/4410) User’s Guide

76

Cooling_DeactOnUpperNonRecov

erTemp

“1”

Enables the function to power off all
blades and drop fan speed after
receiving upper non recoverable (UNR)
thermal events from two different
resources in the C2000 shelf.

Cooling_FanMinimumLevel

“12|15”

Default fan speed in %.
12 - default value for C2000 shelfs.
15 - default value for the other shelfs.

Cooling_InletOutletLowerTemp

erature

“20”

Lower temperature point for inlet/outlet
control

Cooling_InletOutletUpperTemp

erature

“40”

Upper temperature point

Cooling_InletOutletLowerSetP

oint

“10”

Set point at upper temperature

Cooling_InletOutletUpperSetP

oint

“25”

Set point at lower temperature Range 25
to 15, most effect at 15. Influences the
difference between in- and outlet
temperature.

Cooling_InltOutltMinimumSens

orTemperature

“18”

Below this inlet temperature the
inlet/outlet related control is disabled

Cooling_BoardSetPointOffset

“0”

The temperature difference to the
upper-non-critical Threshold of a blade.
E. g. threshold at 85, a 5 would result in
holding the temperature at 80. Allowed
range is 0 to 5

Cooling_BoardConsiderHystere

sis

“0”

“1” subtracts a hysteresis from the set
point

Cooling_BoardMinNumControlle

d

“10”

Minimum number of sensors to be
polled after a temperature event

Cooling_BoardMaxNumControlle

d

“10”

Maximum number of sensors to be
polled Both should not be changed

Table 4-39 Parameters of Cooling System (continued)