2 configuring the cooling management, Table 4-39, Parameters of cooling system – Artesyn System Management Interface Based on HPI-B (Centellis CO 31kX-4100-2000-4410) (June 2014) User Manual
Page 75: Using hpi-b

Using HPI-B
System Management Interface Based on HPI-B (Centellis CO31kX/4100/2000/4410) User’s Guide
75
Configuration option: The configuration parameter 
Cooling_DeactOnUpperNonRecoverTemp
forces to power off all blades and drop fan
speed after receiving nonrecoverable thermal events from two different resources. This option 
is available on C2000 chassis only.
If individual fans fail, the software compensates this by increasing the fan speed of the 
remaining fans accordingly. 
Sensors located on FRUs which have been extracted are no longer considered for the cooling 
management. Furthermore, if a sensor is temporarily not accessible, the software freezes its 
last state and resumes the sensor control based on the frozen data as soon as the connection 
has been reestablished. 
4.5.1.2
Configuring the Cooling Management
The behavior of the cooling management can be configured via entries in the configuration file 
/etc/bbs-hpib/bbs-hpib.conf
. All entries which are related to the cooling
management start with the prefix Cooling_.
The cooling system can be influenced by the parameters listed in the
.
Reboot the Shelf Manager or restart the HPI daemon with sv_stop and sv_start 
commands in order to activate the modified configuration. Assure that the active Shelf 
Manager works with the modified configuration file.
Table 4-39 Parameters of Cooling System
Parameter Name
Default Value
Description
OPENHPI_LOG_DEBUG_FACILITIES
“”
"ipmicooling" enables logging. It enables 
the shelf manager to log the cooling 
related information into files 
/var/log/bbs-hpib0X.log
where
X
can be in the range of 0 to
OPENHPI_LOGFILE_MAX
as
mentioned in the /etc/bbs-
hpib/bbs-hpib.conf 
configuration
file.
