DeviceNet Remote I/O Communication Module RTU-DNET

DVP-PLC Application Manual

7

OFF

When DeviceNet is off, the I/O data in

the buffer area will be cleared.

IN0

ON

When DeviceNet is off, the I/O data in

the buffer area will be held.

IN1 Reserved

Note:

z Please set up the function switch when the power is switched off. After the setup is completed, re-power

RTU-DNET.

z When RTU-DNET is operating, changing the setting of the function switch will be invalid.

z Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.

2.7 Extension Port

The extension port is used on connecting RTU-DNET to DVP Slim DI/DO extension units and special modules.

3 Basic

Operation

3.1 Connecting RTU-DNET to DVP Slim DI/DO Extension Unit

z Open the fixing clips on top and bottom of RTU-DNET. Meet the extension port of Slim DI/DO with RTU-DNET.

z Press the fixing clips on top and bottm of Slim DI/DO and check if the connection is fine.

R

T

U

-D

N

E

T

D

V

P

-1

6

S

P

D

V

P

-0

2

D

A

R

T

U

-D

N

E

T

D

V

P

-1

6

S

P

D

V

P

-0

2

D

A

3.2 Installing RTU-DNET and DVP Slim DI/DO on DIN Rail

z Use 35mm DIN rail.

z Open the DIN rail clip on RTU-DNET and Slim DI/DO. Insert RTU-DNET and Slim DI/DO onto the DIN rail.

z Clip up the DIN rail clips on RTU-DNET and Slim DI/DO to fix them on the DIN rail, as shown below.