Devicenet remote i/o communication module rtu-dnet, 1 how to construct devicenet by rtu-dnet, Dvp-plc application manual 22 – Delta Electronics RTU-DNET User Manual
Page 24: The devicenet network
![background image](/manuals/75066/24/background.png)
DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
22
5
How to Construct a DeviceNet Network Using RTU-DNET
In this section, we will explain how to configure RTU-DNET and the I/O mapping relation between RTU-DNET
and DVPDNET-SL by an application example.
5.1 How to Construct DeviceNet by RTU-DNET
1. The DeviceNet network
DeviceNet
DVP28SV
DVPDNET-SL
DVPDNET
DVP28SV
RUN
STOP
Master
R
T
U
-D
N
E
T
D
V
P
-0
2
D
A
D
V
P
-0
8
S
T
D
V
P
-1
6
S
P
D
V
P
-0
4
A
D
D
V
P
-0
4
T
C
D
V
P
-0
4
P
T
DeviceNet
network configuration tool
2. Set up DVPDNET-SL and RTU-DNET according to the table below.
Module
Node address
Baud rate
DVPDNET-SL 1
500
kbps
RTU-DNET 2 500
kbps
3. Pleae check if all Slim DI/DO extension units, special modules and RTU-DNET are working normally, if the
wiring of the entire network is correct, and if the power supply in DeviceNet is normal.
5.2 How to Configure Network by DeviceNet Network Configuration Tool
1. Configuration of RTU-DNET
(1) Open DeviceNetBuilder software, as below: