beautypg.com

Devicenet remote i/o communication module rtu-dnet – Delta Electronics RTU-DNET User Manual

Page 39

background image

DeviceNet Remote I/O Communication Module RTU-DNET

DVP-PLC Application Manual

37

Attribute

ID

Access

rule

Name

Range

Default

Explanation

1

Special module unidentifiable

b5 ~ b15

Reserved

5 Get/Set

Work mode

0 ~ 1

0

Work mode of special module

0: auto 1: custom

6 Get/Set

Number of input data

0 ~ 8

N/A

Number of input data of special modules

connected

7 Get/Set

Number of output
data

0 ~ 8

N/A

Number of output data of special modules
connected

8 Reserved

9

Get

Error code

N/A

Error code in special module

10~19 Reserved

20 Get/Set

Start CR for module

1 input data

N/A

N/A

Start CR for the input data of special
module 1

21 Get/Set

Input data length for

module 1

N/A

N/A

Length of input data of special module 1

22 Get/Set

Start CR for module
2 input data

N/A

N/A

Start CR for the input data of special
module 2

23 Get/Set

Input data length for
module 2

N/A

N/A

Length of input data of special module 2

24 Get/Set

Start CR for module
3 input data

N/A

N/A

Start CR for the input data of special
module 3

25 Get/Set

Input data length for
module 3

N/A

N/A

Length of input data of special module 3

26 Get/Set

Start CR for module
4 input data

N/A

N/A

Start CR for the input data of special
module 4

27 Get/Set

Input data length for
module 4

N/A

N/A

Length of input data of special module 4

28 Get/Set

Start CR for module
5 input data

N/A

N/A

Start CR for the input data of special
module 5

29 Get/Set

Input data length for
module 5

N/A

N/A

Length of input data of special module 5

30 Get/Set

Start CR for module
6 input data

N/A

N/A

Start CR for the input data of special
module 6

31 Get/Set

Input data length for
module 6

N/A

N/A

Length of input data of special module 6

32 Get/Set

Start CR for module
7 input data

N/A

N/A

Start CR for the input data of special
module 7

33 Get/Set

Input data length for
module 7

N/A

N/A

Length of input data of special module 7

34 Get/Set

Start CR for module
8 input data

N/A

N/A

Start CR for the input data of special
module 8

35 Get/Set

Input data length for
module 8

N/A

N/A

Length of input data of special module 8

36 ~ 49

Reserved

50 Get/Set

Start CR for module
1 output data

N/A

N/A

Start CR for the output data of special
module 1

51 Get/Set

Output data length

N/A

N/A

Length of output data of special module 1