Devicenet remote i/o communication module rtu-dnet – Delta Electronics RTU-DNET User Manual
Page 34
![background image](/manuals/75066/34/background.png)
DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
32
LED status
Indication
How to correct
voltage
2. Acquire diagnostic information through
DeviceNetBuilder.
Red light on
Fatal error; errors in
configuration data
Acquire diagnostic information through
DeviceNetBuilder.
6.5 RUN LED
LED status
Indication
How to correct
Off
RTU-DNET in STOP mode
--
Green light on
RTU-DNET in RUN mode
--
Appendix A: DeviceNet Objects RTU-DNET Supports
DeviceNet
objects
Class
Object
0x01 Identity
object
0x02
Message router object
0x03 DeviceNet
object
0x05 Connection
object
0x9A
RTU-DNET setup parameter object
0x9B
Extension module setup parameter object
0x9C
Extension module parameter object
Class 0x01 – Identity object
Class attribute
Attribute ID
Access rule
Name
Data type
1 Get
Revision
UINT
2 Get
MaxInstance UINT
3 Get
NumberofInstances UINT
6 Get
MaxIdClass UINT
7 Get
MaxIdInstance UINT
Instance
Attribute ID
Access rule
Name
Data type
1 Get
VendorId UINT
2 Get
DeviceType UINT
3 Get
ProductCode UINT
4 Get
Revision
MaxRev
MinRev
USINT
USINT
5 Get
Status WORD
6 Get
Sn UDINT
7 Get
ProdName
StrLen
ASCIIStr
USINT
STRING