Devicenet remote i/o communication module rtu-dnet – Delta Electronics RTU-DNET User Manual
Page 11
![background image](/manuals/75066/11/background.png)
DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
9
No.
Item
Unit
Explanation
5
Length of input data
of special module
Word
The length of input data of the special module connected to
RTU-DNET
6
Length of output
data of special
module
Word
The length of output data of the special module connected to
RTU-DNET
7
Length of input I/O
data
Byte
The sum of the length of the status word of RTU-DNET and the
input data of the special module connected to it. One input
channel of the special module occupies 2 bytes. 8 points of the
digital input are counted as 1 byte.
8
Length of output I/O
data
Byte
The sum of the length of the control word of RTU-DNET and
theoutput data of the special module connected to it. One output
channel of the special module occupies 2 bytes. 8 points of the
digital output are counted as 1 byte.
9
Number of special
modules
Unit
The number of special modules connected to RTU-DNET.
Range: 0 ~ 8
10
Diagnostic interval
time
Sec
The interval when RTU-DNET executes diagnosis.
Range: 1 ~ 65, Default: 5 secs
11
Special module
offline treatment
N/A
How RTU-DNET will react when the special module connected
to it is offline. You can choose “Ignored”, “Alarm” or “Stop
DeviceNet IO”. Default: Alarm
12
Special module erro
treatment
N/A
How RTU-DNET will react when it detacts errors. You can
choose “Ignored”, “Alarm” or “Stop DeviceNet IO”. Default:
Alarm
13
Reset RTU-DNET
N/A
Reset the configuration of RTU-DNET to default settings.
14
Add control word
and status word to
I/O data
N/A
For you to decide whether to add control word and status word
to I/O data. When you choose not to do it, the I/O data in
RTU-DNET and DeviceNet master will not include control word
and status word. If you choose to add them in, the I/O data in
RTU-DNET and DeviceNet master will include control word and
status word.
15
Work mode
N/A
For you to set up the work mode of the special module
connected to RTU-DNET. When set to “auto mode”, RTU-DNET
will configure default CR of the special module as DeviceNet I/O
mapping data. When set to “custom mode”, you can configure
any CR in the special module as DeviceNet I/O mapping data.
16
Number of input
data connected
---
The number of input data of the special module connected to
RTU-DNET
17
Number of output
data connected
---
The number of output data of the special module connected to
RTU-DNET
18
Length of input data
Word
The sum of the length of input data of the special modules
connected to RTU-DNET
19
Length of output
data
Word
The sum of the length of output data of the special modules
connected to RTU-DNET
20
I/O mapping
N/A
The I/O mapping relation between RTU-DNET and the special
module connected to it
4.2 Format of Requet Message and Response Message
1.
RTU-DNET supports using DeviceNet explicit messages to poll special modules.
Format of request messages
Byte position
Data written into special module
Data read from special module
0
Frag[0]+XID+MAC ID
Frag[0]+XID+MAC ID