Devicenet remote i/o communication module rtu-dnet – Delta Electronics RTU-DNET User Manual

Page 11

background image

DeviceNet Remote I/O Communication Module RTU-DNET

DVP-PLC Application Manual

9

No.

Item

Unit

Explanation

5

Length of input data

of special module

Word

The length of input data of the special module connected to
RTU-DNET

6

Length of output

data of special

module

Word

The length of output data of the special module connected to
RTU-DNET

7

Length of input I/O

data

Byte

The sum of the length of the status word of RTU-DNET and the
input data of the special module connected to it. One input
channel of the special module occupies 2 bytes. 8 points of the
digital input are counted as 1 byte.

8

Length of output I/O

data

Byte

The sum of the length of the control word of RTU-DNET and

theoutput data of the special module connected to it. One output
channel of the special module occupies 2 bytes. 8 points of the
digital output are counted as 1 byte.

9

Number of special

modules

Unit

The number of special modules connected to RTU-DNET.

Range: 0 ~ 8

10

Diagnostic interval

time

Sec

The interval when RTU-DNET executes diagnosis.
Range: 1 ~ 65, Default: 5 secs

11

Special module

offline treatment

N/A

How RTU-DNET will react when the special module connected

to it is offline. You can choose “Ignored”, “Alarm” or “Stop
DeviceNet IO”. Default: Alarm

12

Special module erro

treatment

N/A

How RTU-DNET will react when it detacts errors. You can
choose “Ignored”, “Alarm” or “Stop DeviceNet IO”. Default:
Alarm

13

Reset RTU-DNET

N/A

Reset the configuration of RTU-DNET to default settings.

14

Add control word

and status word to

I/O data

N/A

For you to decide whether to add control word and status word
to I/O data. When you choose not to do it, the I/O data in
RTU-DNET and DeviceNet master will not include control word
and status word. If you choose to add them in, the I/O data in
RTU-DNET and DeviceNet master will include control word and
status word.

15

Work mode

N/A

For you to set up the work mode of the special module
connected to RTU-DNET. When set to “auto mode”, RTU-DNET
will configure default CR of the special module as DeviceNet I/O
mapping data. When set to “custom mode”, you can configure
any CR in the special module as DeviceNet I/O mapping data.

16

Number of input

data connected

---

The number of input data of the special module connected to
RTU-DNET

17

Number of output

data connected

---

The number of output data of the special module connected to
RTU-DNET

18

Length of input data

Word

The sum of the length of input data of the special modules
connected to RTU-DNET

19

Length of output

data

Word

The sum of the length of output data of the special modules
connected to RTU-DNET

20

I/O mapping

N/A

The I/O mapping relation between RTU-DNET and the special
module connected to it

4.2 Format of Requet Message and Response Message

1.

RTU-DNET supports using DeviceNet explicit messages to poll special modules.

„ Format of request messages

Byte position

Data written into special module

Data read from special module

0

Frag[0]+XID+MAC ID

Frag[0]+XID+MAC ID