DeviceNet Remote I/O Communication Module RTU-DNET

DVP-PLC Application Manual

6

2.3 DeviceNet Connection Port

The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with RTU-DNET.

PIN

Signal

Color

Content

1 V- Black

0

VDC

2 CAN_L Blue Signal-

3 SHIELD

-

Shielded

4 CAN_H White Signal+

5 V+ Red 24

VDC

1

2

3

4

5

2.4 RUN/STOP Switch

RUN/STOP action

Explanation

STOP → RUN

1. Re-detecting the extension module.

2. Reading/writing the data in the extension

module.

RUN → STOP

Stop reading/writing the data in the extension
module.

RUN

STOP

2.5 Address Switch

The switch is used on setting up the node address of RTU-DNET on DeviceNet. Range: 00 ~ 63 (64 ~ 99 are

forbidden).

Switch setting

Content

0 ~ 63

Valid DeviceNet node address

64 ~ 99

Invalid DeviceNet node address

9

1

6

4

5

0

0

9

1

3

2

7

8

2

5

6

4

3

7

8

Example: If you need to set the node address of RTU-DNET to 26, simply switch the corresponding switch of x10

1

to 2 and the corresponding switch of x10

0

to 6.

Note:

z Please set up the node address when the power is switched off. After the setup is completed, re-power

RTU-DNET.

z When RTU-DNET is operating, changing the setting of node address will be invalid.

z Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.

2.6 Function Switch

The function switches are for:

z Setting up data retention function (IN0)

z Setting up the baud rate of DeviceNet (DR0 ~ DR1)

DR1

DR0

Baud rate

OFF OFF

125

kbps

OFF ON

250

kbps

ON OFF

500

kbps

ON ON

Incorrect

setting