DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
38
Attribute
ID
Access
rule
Name
Range
Default
Explanation
for module 1
52 Get/Set
Start CR for module
2 output data
N/A
N/A
Start CR for the output data of special
module 2
53 Get/Set
Output data length
for module 2
N/A
N/A
Length of output data of special module 2
54 Get/Set
Start CR for module
3 output data
N/A
N/A
Start CR for the output data of special
module 3
55 Get/Set
Output data length
for module 3
N/A
N/A
Length of output data of special module 3
56 Get/Set
Start CR for module
4 output data
N/A
N/A
Start CR for the output data of special
module 4
57 Get/Set
Output data length
for module 4
N/A
N/A
Length of output data of special module 4
58 Get/Set
Start CR for module
5 output data
N/A
N/A
Start CR for the output data of special
module 5
59 Get/Set
Output data length
for module 5
N/A
N/A
Length of output data of special module 5
60 Get/Set
Start CR for module
6 output data
N/A
N/A
Start CR for the output data of special
module 6
61 Get/Set
Output data length
for module 6
N/A
N/A
Length of output data of special module 6
62 Get/Set
Start CR for module
7 output data
N/A
N/A
Start CR for the output data of special
module 7
63 Get/Set
Output data length
for module 7
N/A
N/A
Length of output data of special module 7
64 Get/Set
Start CR for module
8 output data
N/A
N/A
Start CR for the output data of special
module 8
65 Get/Set
Output data length
for module 8
N/A
N/A
Length of output data of special module 8
Common services
Implemented for
Service code
Class
Instance
Service name
0x0E Yes
Yes
Get_Attribute_Single
0x10 No
Yes
Set_Attribute_Single
Class 0x9C – Extension module parameter object
Class attribute
Attribute ID
Access rule
Name
Data type
1 Get
Revision UINT
2 Get
MaxInstance UINT
Instance 1 ~ 8 (CR fpr the 1
st
~ 8
th
special module)
Attribute ID
Access rule
Name
Data type
1
Get
Content in CR#0
UINT
2 Get/Set
Content in CR#1
UINT
3 Get/Set
Content in CR#2
UINT