beautypg.com

2 overview, 1 module structure, 1 module features – Pilz PSSu K F FCU User Manual

Page 7: Section 2, Overview, Module structure, Module features

background image

Overview

Operating Manual PSSu K F FCU
1002391-EN-04

7

Overview

Module structure

The module combines the function unit (inputs or outputs) and connection levels in one
housing.
Wiring is via 10-pin connectors with spring-loaded terminals, which are plugged into the
connector strips on the module.
Details of the applicable connectors with spring-loaded terminals are available in the chap-
ter entitled "Intended Use".

Module features

}

For failsafe applications in system environment B (automation system PSS 4000)

}

12 Digital inputs, 8 of which are for fast shutdown

}

Filter time can be configured separately for inputs with and without fast shutdown

}

2 Independent test pulse outputs that use different test pulses

}

2 Digital outputs

– Semiconductor technology
– Single-pole
– Positive-switching
– Current load capacity per output: 2,00 A
– Short circuit-proof
– Overload-proof
– Free from feedback

}

2 Dual-pole digital outputs

– Semiconductor technology
– Switches to 24 V (Ox+) and 0 V (Ox-)
– Current load capacity: 3,0 A
– Short circuit-proof
– Overload-proof
– High discharge voltage
– Free from feedback

}

LEDs for:

– Switch status of each input/output
– Module error
– Module status

}

4 x 10-pin connector strip

Accessories:

}

Connector with spring-loaded terminals (necessary for operation)

}

Labelling bracket

2

2.1

2.1.1