Inputs
312435
Number
12
Input current range
2,5 - 7,5 mA
Min. threshold voltage when signal changes from "1"
to "0"
9,0 V
Max. threshold voltage when signal changes from "0"
to "1"
10,0 V
Max. processing time of input when signal changes
from "1" to "0" (depending on the configured input fil-
ter time)
2,700 - 5,800 ms
Max. processing time of input when signal changes
from "0" to "1" (depending on the configured input fil-
ter time)
2,700 - 5,800 ms
Potential isolation between input and voltage for the
internal module bus
Yes
Test pulse outputs
312435
Number of test pulse outputs
2
Voltage, test pulse outputs
24 V DC
Short circuit-proof
Yes
Number of outputs that can be configured as test
pulses
2
Max. output current at "1" signal
0,25 A
Max. cable runs between test pulse output and input
200 m
Standard for voltage interruptions
DIN V EN V 1954, EN61131-2, EN61496-1
Semiconductor outputs
312435
Number of positive-switching single-pole semicon-
ductor outputs
2
Voltage
24,0 V
Typ. output current at “1” signal and rated voltage of
semiconductor output
2,00 A
Permitted current range
0,00 - 2,50 A
Residual current at "0" signal
0,02 A
Max. transient pulsed current
6 A
Max. internal voltage drop
100 mV
Monitoring threshold of semiconductor output
9,0 V
Max. duration of on time during self test
200 µs
Max. duration of off time during self test
200 µs
Max. processing time of semiconductor output when
signal changes from "1" to "0"
0,250 ms
Max. processing time of semiconductor output when
signal changes from "0" to "1"
0,450 ms
Potential isolation from system voltage
Yes
Potential isolation between semiconductor output and
input
Yes
Short circuit-proof
Yes
Permitted loads
Inductive, capacitive, resistive
Semiconductor outputs, 2-pole
312435
Number of dual-pole semiconductor outputs
2
Permitted current range
0,00 - 3,50 A