beautypg.com

Spectrum Controls 1734sc-IE2CH User Manual

Page 14

background image

2-2

Point IO™ 2/4 Channel Analog HART Module



User’s Manual Pub. 0300257-01 Rev. A

5 VDC 24 VDC

15 mA

20 mA

Use the table below to determine the maximum number of IExCH modules that can be
installed in a MicroLogix system.

Section 2.3
General
Considerations

1734 I/O is suitable for use in an industrial environment when installed in accordance
with these instructions. Specifically, this equipment is intended for use in clean, dry
environments Pollution degree 2

1

and to circuits not exceeding Over Voltage Category

II

2

(IEC 60664-1)

3

.

2.3.1

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-
hazardous locations only. The following WARNING statement applies to use in
hazardous locations.

!

Attention

EXPLOSION HAZARD

Substitution of components may impair suitability for Class I,
Division 2.

Do not replace components or disconnect equipment unless
power has been switched off or the area is known to be non-
hazardous.

Do not connect or disconnect components unless power has
been switched off or the area is known to be non-hazardous.

This product must be installed in an IP54 rated enclosure.

All wiring must comply with N.E.C. article 501-4(b).




1

Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that

occasionally a temporary conductivity caused by condensation shall be expected.

2

Over Voltage Category II is the load level section of the electrical distribution system. At this level

transient voltages are controlled and do not exceed the impulse voltage capability of the product’s
insulation.

3

Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)

designations.

This manual is related to the following products: