Chapter 1: Module Overview

1-3

User’s Manual Pub. 0300257-01 Rev. A

1.5.1

LED Indicators

The 1734 analog HART module uses several LEDs to show operational status. The
status LEDs are defined below:

Table 1-1 (LED Status Indicators)

Indicator State

Description

Module Status

Off

No power applied to device

Green

Device operating normally

Flashing Green

Device needs commissioning due to configuration
missing, incomplete, or incorrect

Flashing Red

Unrecoverable fault may require device replacement.

Red Recoverable

fault.

Flashing Red/Green Device is in self-test mode.

Network status Off

Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator

Flashing Green

Device is on-line but has no connections in the
established state.

Green

Device on-line and has connections in the established
state.

Flashing Red

One or more I/O connections in timed-out state

Red

Critical link failure - failed communication device.
Device detected error that prevents it communicating
on the network.

Flashing
Red/Green

Communication faulted device - the device has
detected a network access error and is in
communication faulted state.

Channel status Off

Channel not in use

Solid Green

Normal (channel scanning inputs)

Flashing Green

Channel receiving HART data

Solid Red

No power or major channel fault

Flashing Red

Channel at end of range

Flashing Red/Green Hart device error on HART enabled channel

Section 1.6
System
Overview

The module communicates to the controller via a 1734 Control Net, Device Net or
Ethernet adapter. The module receives 5 and 24V dc power through the bus interface.

Note: No external power supply is required for 2-wire input transmitters.

1.6.1

Module Power-up

At power-up, the module performs a check of its internal circuits, memory, and basic