beautypg.com

EXFO IQS-600 Integrated Qualification System User Manual

Page 144

background image

Preparing for Automation

136

IQS-600

Getting Optimum Performance from Your Integrated Qualification System

For information on cabling, see Preparing Hardware for GPIB Control on
page 132.

Bus timing (GPIB control only): Required if you intend to work with
IEEE 488.1, for it affects the handshake rate of this protocol. It indicates
the minimum amount of time a GPIB controller waits, once data is
placed on the bus, before setting the data valid bus line (DAV) to true.

The possible bus timings are:

If your setup supports it, select the very-high-speed timing to get the
best performance.

Output unit (GPIB, RS-232, ActiveX and TCP/IP): The IQS controller
unitcan return results in

linear units (for example, watts)

log units (for example, dBm)

Since internal units are linear, you will get optimal performance by
using linear units for output (no need for an internal conversion to log).

Note: You must make the choice of output unit for each instrument offering such

a feature. Refer to the user guide of each optical instrument for a list of
available commands and queries.

Mode

Bus timing delay

Normal

1100 ns

High speed

500 ns

Very high speed

350 ns