DLP- E109 Drill Holes to Anchor and Provide Access to the Bay Assembly

Figure 17-1

Floor Template

Step 2

Use the corner indicators “C” to determine the closest recommended position of an adjacent 900-mm
(35.4-inch) bay assembly.

Step 3

Use a marking pen to mark the floor with the corner indicators appropriate to your installation.

Step 4

At the four locations marked “D,” drill floor bolt holes according to the bolt manufacturer’s
recommendation for bolt hole size.

Step 5

If you will use under-floor power, use the drill and saw to cut out the rectangular floor areas marked “E.”

Step 6

If you will route optical cables in a 900-mm (35.4-inch) bay from under the floor, use the drill and saw
to cut out the rectangular floor areas marked “F.”

Step 7

If you will route optical cables in a 600-mm (23.6-inch) bay from under the floor, use the drill and saw
to cut out the rectangular floor areas marked “J.”

Step 8

If you will route any timing, alarm, or LAN cables through the floor to the customer access panel (CAP),
use the drill to cut out the floor areas marked “G.”

Step 9

(Optional.) If you want to create other access holes for under-floor access (for AC power, for example),
use the reciprocating saw to cut sufficient holes within any of the locations marked “H.”

Step 10

Return to your originating procedure (NTP).

83488

C

B

A

A

B

C

G

G

D

H

H

H

H

F

F

E

E

D

C

B

A

A

B

C

J

J

D

H

FRONT

H

F

F

D

UNDERFLOOR SYSTEM CABLE

UNDERFLOOR SYSTEM CABLE

UNDERFLOOR CMP CABLE

UNDERFLOOR CMP CABLE

OPTICAL CABLE ACCESS

OPTICAL CABLE ACCESS

OPTICAL CABLE ACCESS

UNDERFLOOR POWER

UNDERFLOOR POWER

UNDERFLOOR NETWORK CABLE

UNDERFLOOR NETWORK CABLE

CABLE ROUTING MODULE

CABLE ROUTING MODULE

ADJACENT RACK

ADJACENT RACK

Bolt Hole
Pattern

600 mm Footprint

900 mm Footprint

Adjacent Rack