Table 7 — Minimum Outdoor-Air Operating

Temperature

English

09DK—

HEAD

PRESSURE

CONTROL

TD

° F

COMPRESSOR CAPACITY (%)*

100 1 75 1 50 1 25

Minimum Outdoor-Air

Temperature ° F

All

Sizes

FCPSs and

Motormaster®

III

30
25
20

-20

-20

-20

-20

054,

064

FCPSst

2 Fans

30
25
20

29
38
47

34
40
47

38
42
46

51

53
56

074,

084

FCPSst

2 Fans

ATSs

2 Fans

30
25
20

12
22

31

19
25

31

22
29
36

43
47

51

SI

09DK—

HEAD

PRESSURE

CONTROL

TD

° C

COMPRESSOR CAPACITY (%)*

100 1 75 1 50 1 25

Minimum Outdoor-Air

Temperature ° C

All

Sizes

FCPSs and

Motormaster

III

16.7
13.9
11 1

-29

-29

-29

-29

054,

064

FCPSst

2 Fans

16.7
139
11 1

-2

3
8

1

4
8

3
6
8

11

12
13

074,

084

FCPSst

2 Fans

ATSs

2 Fans

167
139
11 1

-11

-6

-1

-7
-4

-1

-6
-2

2

6
8

11

LEGEND

ATS

— Air Temperature Switch

FCPS

— Fan Cycling Pressure Switch

TD

— Temperature Difference = Saturated Condensing

Temperature Entering - Entering-Air Temperature

'Interpolation permitted.
tAdditional FCPSs needed for 67/33, 33/33/33, and 33/33/17/17%

capacity split applications

NOTES:

1. Fans or the 09DK054-084 units are controlled by ATSs and FCPSs.

See Table 8 for more details.

2 Minimum outdoor temperatures are determined for indoor and out­

door unit combinations of the same capacity.

Table 8 — Fan Cycling Controls Temperature/

Pressure Settings

English

FCPS

OPENS AT 160

ATS

UNIT 09DK—

±10 psig

OPENS AT 70 ± 3° F

CLOSES AT 260

±15 psig

CLOSES AT 80 ± 3° F

054,064

FM 3,4'

074,084

FM 3,4'

FM 5,6t

SI

FCPS

OPENS AT 1103

ATS

UNIT 09DK—

± 69 kPa

OPENS AT 21.1 ± 1.7°C

CLOSES AT 1793

± 103 kPa

CLOSES AT 26.7 ± 1.7° C

054,064

FM 3,4*

...

074,084

FM 3,4*

FM 5,6t

LEGEND

ATS

— Air Temperature Switch

FCPS

— Fan Cycle Pressure Switch

FM

— Fan Motor

'Fan motors 3 and 4 are each controlled by a FCPS for 100 and

50/50% capacity split applications. For other capacity split options,
the accessory fan control kit must be used and additional FCPS's
are required. See accessory fan control kit installation instructions
for more information

fFan motors 5 and 6 are each controlled by an ATS.