beautypg.com

Carrier 09DK054-084 User Manual

Page 21

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 3 — Available Liquid Lift Ft (m)

REFRIGERANT

R-22

R-502

R-134A

Temperature Difference F (C)

UNIT

20

(11.1)

30

(16.7)

20

(11.1)

30

(16.7)

20

(11.1)

30

(16.7)

054

60

(18.3)

50

(15 2)

60

(18.3)

44

(13.4)

29

(8.8)

26

(7.9)

09DK

064

41

(12 5)

31

(9.5)

41

(12.5)

25

(7 6)

20

(6.1)

6

(1.8)

074

44

(13.4)

34

(10.4)

44

(13.4)

28

(8.5)

18

(5.5)

7

(2.1)

084

51

(15.6)

41

(12.5)

51

(15.6)

35

(10.7)

22

(6.7)

10

(3 1)

NOTES:

1 The liquid lift data allows for a 7 psi (48 kpa) drop for liquid line

accessories, and a 2° F (1.rC), iiquid line ioss with maximum
change.

2. Temperature difference = Saturated condensing temperature (en­

tering) — Entering-air temperature (dry buib) in degree F (° C)

3. The liquid iift data is based on 15° F (8 3° C) subcooiing, 95 F

(35 C) entering-air temperature, and a 50/50% capacity split ap-
piication Subcooling based on condenser subcooling = Satu­
rated condensing temperature entering - Actual temperature leaving
the coii

Step 4 — Complete Electrical Connections

GENERAL — Verify nameplate electrical requirements match
available power supply. Voltage at condenser must be within
the minimum and maximum shown in Table 4 and phases
must be balanced within 2%. Contact local power company
for line voltage corrections. Never operate a motor where a
phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent voltage
imbalance:

max voltage deviation

% Voltage _

from average voltage

Imbalance

^ average voltage

Example: Supply voltage is 240-3-60.

AB = 243

V

BC = 236

V

AC = 238 V

Average Voltage

243 -F 236 -f 238

^ 717

3

= 239

V

Determine maximum deviation from average voltage:

(AB) 243 - 239 = 4 V
(BC) 239 - 236 = 3

V

(AC) 239 - 238 = 1

V

Maximum deviation is then 4 v. To determine the percent
voltage imbalance:

4

% Voltage Imbalance = 100 x----------

239

= 1.7%

This amount of phase imbalance is satisfactory since it is

below the maximum allowable of 2%.

IMPORTANT: If supply voltage phase imbalance is
more than 2%, contact your local electric utility com­
pany immediately.

Condenser operation on improper line voltage or exces­

sive phase imbalance may be considered abuse and any re­
sulting damage may not be covered by Carrier warranty.

All wiring must be in accordance with local or NEC

(National Electrical Code) regulations.

FIELD CONNECTIONS - Refer to Table 4 and Fig. 14,

18, and 25 for field wiring details.

100

%

Fig. 17 - 100% Coil Circuiting; 074 Units

21