6-2

151267

6.1.1

Terminal Strip 1

This sections describes what the terminal connections of terminal strip 1 are used for.

Terminal

Number

Name

Description

1

+24 VDC

Positive 24 VDC in or out.

2

GND

Ground

3

Trouble Out

Trouble output, active low.

4

GND

Ground

5

Select All

Not Used

6

Not Used

7

8

GND

Ground

9

GND

Ground

10

Alarm Active

Signal input from main DMR to indicate when an Alarm occurs. Active low.

11

Alarm Select 1

Used by FACP for automatic alarm control of zone outputs. Active low.

12

Alarm Select 2

13

Alarm Select 3

14

Alarm Select 4

15

Alarm Select 5

16

Alarm Select 6

17

GND

Ground

18

MIC Active

Signal input from main DMR to indicate when the microphone has been
activated. Active low.

19

Not Used

Not Used

20

Not Used

21

Not Used

22

Not Used

23

Not Used

24

Not Used