Section 3
Installation

This section of the manual is intended to help you plan your tasks to facilitate the installation.
Please read this section thoroughly, especially if you are installing a SKE-450 control for the
first time.

3.1

Environmental Specifications

It is important to protect the SKE-450 control panel from moisture. To prevent damage, the
following conditions should be avoided when installing the units:

Mount indoors in dry locations only

Do not mount directly on exterior walls, especially masonry walls (condensation)

Do not mount directly on exterior walls below grade (condensation)

Protect from plumbing leaks

Protect from splash caused by sprinkler inspection ports

Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)

When selecting a location to mount the panel, it should be mounted where it will NOT be
exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity equal to or
greater than 93% at 30°C (89°F) noncondensing.

3.2

Electrical Specification

* Specify voltage requirements when ordering.

Note: Refer to the control panel wiring diagram to determine which power source is required for your control.

Table 3-1: Electrical Specifications

Circuit

Rating

Operating Voltage

120 Vrms @ 60 Hz @ 1.2 amp
*230 Vrms @ 50Hz @ .607 amp

Battery Charging Voltage/Circuit

27.4 VDC @ 1.9A max/ 0.75 avg

Trouble Relays

2.5 A @ 30 VDC resistive

Minimum Low AC Detect

92VAC 25V System
94VAC 70.7V System