Section 3
Installation
This section of the manual is intended to help you plan your tasks to facilitate the installation.
Please read this section thoroughly, especially if you are installing a SKE-450 control for the
first time.
3.1
Environmental Specifications
It is important to protect the SKE-450 control panel from moisture. To prevent damage, the
following conditions should be avoided when installing the units:
•
Mount indoors in dry locations only
•
Do not mount directly on exterior walls, especially masonry walls (condensation)
•
Do not mount directly on exterior walls below grade (condensation)
•
Protect from plumbing leaks
•
Protect from splash caused by sprinkler inspection ports
•
Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the panel, it should be mounted where it will NOT be
exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity equal to or
greater than 93% at 30°C (89°F) noncondensing.
3.2
Electrical Specification
* Specify voltage requirements when ordering.
Note: Refer to the control panel wiring diagram to determine which power source is required for your control.
Table 3-1: Electrical Specifications
Circuit
Rating
Operating Voltage
120 Vrms @ 60 Hz @ 1.2 amp
*230 Vrms @ 50Hz @ .607 amp
Battery Charging Voltage/Circuit
27.4 VDC @ 1.9A max/ 0.75 avg
Trouble Relays
2.5 A @ 30 VDC resistive
Minimum Low AC Detect
92VAC 25V System
94VAC 70.7V System