beautypg.com

Input circuits -13, 1 cmd1 input circuit -13, 1 class b (style y) -13 – SilentKnight SKE-450 Voice Evacuation Control Panel User Manual

Page 23: 7 input circuits, 1 cmd1 input circuit, 1 class b (style y)

background image

Installation

151267

3-13

3.7

Input Circuits

The SKE-450 has two command input circuits (CMD1 & CMD2). The command input
circuits are used to activate the amplifier that transmits the audio signal over the output
speakers.

3.7.1

CMD1 Input Circuit

This section describes how to connect Class B (Style Y) or Class A (Style Z) inputs to CMD1
terminals. CMD1 input circuit rating is 12 to 30 VDC @ 50 mA. CMD1 is a polarity reverse
input to activate and supervise the SKE-450

3.7.1.1

Class B (Style Y)

Figure 3-10 illustrates how to wire a Class B (Style Y) input circuit to CMD1 input.

Figure 3-10 Class B (Style Y) CMD1 Input Circuit Configuration

Supervised

Power Limited

4.7 k

Ω EOL

UL Listed
Model 7626

Note: The 4.7 k

Ω EOL

is typically used with
Silent Knight Controls.
Check the Installations
Manual of the FACP
you are using to
determine EOL value.

If a trouble condition
exists on the SKE-450,
the supervision circuit is
opened in addition to
energizing the trouble
relay causing a trouble at
the FACP.