5 system leds -6, 5 system leds – SilentKnight SKE-450 Voice Evacuation Control Panel User Manual
Page 16

SKE-Series Voice Evacuation System Installation/Operation Manual
3-6
151267
3.3.5
System LEDs
The control panel has LEDs which indicate system operation, alarms, and trouble conditions.
Table 3-5 lists the LEDs and their function. See also .
Figure 3-3 System LEDs Close-up View
Table 3-5: LED Descriptions
LED Name
Color
Description
Comments
Speaker Trouble Yellow
ON = Speaker circuit trouble
OFF = Speaker/amp is operating normally
Trouble relay energized.
Alarm
Red
ON = Alarm
OFF = No alarms
Either CMD1 and/or CMD2 are activated.
Mic Trouble
Yellow
ON = Trouble with on-board microphone
OFF = Microphone connected
Flashing = Trouble with remote
microphone
Trouble relay energized.
CMD2 Trouble
Yellow
ON = Trouble condition with CMD2
input, EOL trouble
OFF = CMD2 operating properly
Trouble relay energized.
Earth Ground
Yellow
ON = Earth Ground Fault detected
OFF = No Earth Ground Fault detected
Trouble relay energized.
Battery Status
Yellow
ON = Low Battery
OFF = Battery OK
Trouble relay energized.
Power
Green
ON (Steady) = Power is present
Flashing = No AC power to the control.
Trouble relay energized immediately on trouble
unless AC Delay is enabled, in which case, trouble
relay will energize in 2 hours.
Speaker Trouble
Alarm
Mic Trouble
CMD2 Trouble
Earth Ground Trouble
Power
Battery Status