beautypg.com

Section 4 programming, Dip switch programming -1, 1 dip switch programming – SilentKnight SKE-450 Voice Evacuation Control Panel User Manual

Page 29

background image

151267

4-1

Section 4
Programming

This section of the manual describes how to program the SKE-450 using the programming
DIP switches.

4.1 DIP Switch Programming

Table 4-1 lists the programming DIP switches, and describes what each of their settings
accomplish.

Table 4-1: DIP Switch Programming

DIP

Switch

Function

Switch Number

Setting

Comments

1

2

3

4

5

6

7

8

SW1

Initial Message
Delay

off

off

off

0 Seconds

This option selects the
initial delay before the
message starts playing
after an alarm. The
tone sounds during the
delay.

For UL 864
installations, this
option must be set to a
minimum of 8 seconds.

on

off

off

4 Seconds

off

on

off

8 Seconds

on

on

off

12 Seconds

off

off

on

16 Seconds

on

off

on

20 Seconds

off

on

on

24 Seconds

on

on

on

28 seconds

Delay Between
Messages

off

off

4 Seconds

This option selects the
amount of time
between messages.

on

off

8 Seconds

off

on

12 Seconds

on

on

16 Seconds

Message
Repeat

off

off

off

None

This option selects the
total number of times
that the message will
be repeated.

For UL 864
installations, this
option must be set to a
minimum of 3.

on

off

off

1

off

on

off

2

on

on

off

3

off

off

on

4

on

off

on

5

off

on

on

6

on

on

on

Continuously