Section 4 programming, Dip switch programming -1, 1 dip switch programming – SilentKnight SKE-450 Voice Evacuation Control Panel User Manual
Page 29

151267
4-1
Section 4
Programming
This section of the manual describes how to program the SKE-450 using the programming
DIP switches.
4.1 DIP Switch Programming
Table 4-1 lists the programming DIP switches, and describes what each of their settings
accomplish.
Table 4-1: DIP Switch Programming
DIP
Switch
Function
Switch Number
Setting
Comments
1
2
3
4
5
6
7
8
SW1
Initial Message
Delay
off
off
off
0 Seconds
This option selects the
initial delay before the
message starts playing
after an alarm. The
tone sounds during the
delay.
For UL 864
installations, this
option must be set to a
minimum of 8 seconds.
on
off
off
4 Seconds
off
on
off
8 Seconds
on
on
off
12 Seconds
off
off
on
16 Seconds
on
off
on
20 Seconds
off
on
on
24 Seconds
on
on
on
28 seconds
Delay Between
Messages
off
off
4 Seconds
This option selects the
amount of time
between messages.
on
off
8 Seconds
off
on
12 Seconds
on
on
16 Seconds
Message
Repeat
off
off
off
None
This option selects the
total number of times
that the message will
be repeated.
For UL 864
installations, this
option must be set to a
minimum of 3.
on
off
off
1
off
on
off
2
on
on
off
3
off
off
on
4
on
off
on
5
off
on
on
6
on
on
on
Continuously