beautypg.com

Warning – Reznor R6GP Unit Installation Manual User Manual

Page 8

background image

8

Air Filter Requirements

WARNING:

Never operate the unit without a filter in place.

Dust and lint could accumulate on internal

parts, resulting in loss of efficiency, equipment
damage and possible fire.

All return air must pass through the filters before entering
the unit. It is important that all filters be kept clean and
replaced frequently to ensure proper operation of unit.
Dirty or clogged filters will reduce the efficiency of the
unit and result in unit shutdowns. Air filter pressure drop
must not exceed 0.08 inches WC. When replacing the air
filters, a suitable air filter must be installed ahead of the
evaporator coil of the return air system. Refer to Table 1
for recommended filter sizes.

Figure 3. Bottom View

Crate Brackets (x4)

Long Bottom

Boards (x2)

Short Bottom
Boards (x2)

Base
Rails

Figure 2. Side View

Wood Cap

Assembly

Top Crate
Brackets

Lower
Crate
Brackets

End Skid

Side Skids

UNIT

FACTORY

FILTER SIZE

QTY

R6GP-072*-(100/166)C

16x20x2

4

R6GP-090*-200C

16x20x2

4

R6GP-120*-235C

16x25x2

4

Table 1. Filter Sizes & Quantities

UNIT INSTALLATION

Packaging Removal

All units have been securely packaged at the point of
shipment. After unpacking the unit, carefully inspect for
apparent and concealed damage. Claims for damage
should be filed with the carrier by the consignee.

1. Remove top crate brackets and wooden cap assembly

from top of unit (Figure 2).

2. Remove lower crate brackets, 4 side skids, and 2 end

skids from each side of unit. NOTE: DO NOT remove

base rails from unit.

3. Rig unit and raise up approximately 4 feet off the ground.
4. Remove crate brackets (Figure 3) securing long and

short bottom boards to underside of unit. NOTE: Some

screws are located in fork slots.

5. Remove long & short bottom boards from beneath unit.
6. Inspect unit thoroughly for shipping damage.
7. Carefully lower and position unit to it’s permanent

location.

Rigging & Hoisting

WARNING:

To avoid the risk of property damage, personal
injury, or death, it is the rigger’s responsibility
to ensure that whatever means are used to hoist
the unit are safe and adequate:

• The lifting equipment must be adequate for the

load. Refer to Table 3 (page 27) for unit weights.

• The unit must be lifted from the holes in the

base rails using cables or chains.

• Spreader bars are required to protect the unit

and ensure even loading. See Figure 4.

• Keep the unit in an upright position at all times.

The rigging must be located outside the units

center of gravity. Refer to Figures 12 - 14 (pages

22 - 27) for locating the center of gravity.

• All panels must be securely in place during

rigging and hoisting.

Minimum Clearance Requirements

R6GP units are certified as combination heating and
cooling equipment for outdoor installation only. Figure 5
(page 9) displays the minimum clearances to combustible
materials for both Downflow and Horizontal discharge.

R6GP units may be installed on non-combustible surfaces
when used with bottom supply and return air ducts.

Units may be installed on wood flooring or on Class A,