Table 7. R6GP-072C-166C Series - Downflow Configuration

R6GP-072(C/D)-166C

Factory Standard: 1Hp Downflow Performance Chart

‡ Indicates Factory Sheave Setting

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns
Open

5

Turns

Open ‡

5.5

Turns
Open

6

Turns
Open

0.1

CFM

3025

2872

RPM

721

719

kW

0.88

0.80

0.2

CFM

2989

2832

2674

RPM

775

749

722

kW

0.92

0.83

0.74

0.3

CFM

2936

2788

2613

2437

RPM

802

776

751

725

kW

0.94

0.85

0.76

0.68

0.4

CFM

2879

2708

2537

2335

2132

RPM

831

804

777

753

728

kW

0.96

0.87

0.79

0.68

0.57

0.5

CFM

2826

2647

2437

2227

2016

RPM

857

834

808

782

756

kW

0.99

0.87

0.78

0.68

0.59

0.6

CFM

2769

2544

2318

2107

1895

RPM

881

860

838

811

784

kW

1.04

0.90

0.77

0.67

0.57

0.7

CFM

2625

2395

2220

2044

RPM

909

887

864

840

kW

1.01

0.86

0.78

0.70

0.8

CFM

2525

2323

2120

1920

RPM

937

915

892

868

kW

1.01

0.89

0.77

0.68

0.9

CFM

2449

2216

2004

RPM

964

941

919

kW

1.01

0.88

0.79

1.0

CFM

2160

1928

RPM

971

946

kW

0.92

0.81

1.1

CFM

RPM

kW

1.2

CFM

RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil

For operation at 208V: Deduct approximately 0.5% from Cfm