Table 5. R6GP-072C-100C Series - Downflow Configuration

R6GP-072(C/D)-100C

Factory Standard: 1Hp Down-flow Performance Chart

‡ Indicates Factory Sheave Setting

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns
Open

5

Turns

Open ‡

5.5

Turns
Open

6

Turns
Open

0.1

CFM

2946

2793

RPM

741

715

kW

0.85

0.77

0.2

CFM

2867

2728

2588

RPM

771

745

719

kW

0.85

0.78

0.72

0.3

CFM

2975

2828

2680

2528

2375

RPM

824

800

775

749

722

kW

0.98

0.88

0.79

0.72

0.65

0.4

CFM

2763

2608

2453

2293

2110

RPM

828

804

780

746

726

kW

0.95

0.84

0.72

0.63

0.57

0.5

CFM

2727

2582

2381

2180

1982

RPM

854

831

808

784

750

kW

0.95

0.86

0.75

0.65

0.56

0.6

CFM

2680

2488

2295

2105

1860

RPM

880

858

835

801

786

kW

0.97

0.86

0.76

0.63

0.54

0.7

CFM

2582

2399

2177

1955

RPM

908

884

862

839

kW

0.98

0.86

0.76

0.66

0.8

CFM

2528

2301

2074

1913

RPM

936

912

888

866

kW

0.97

0.86

0.76

0.68

0.9

CFM

2417

2220

2111

RPM

960

940

908

kW

1.02

0.85

0.79

1.0

CFM

2105

1854

RPM

964

944

kW

0.88

0.77

1.1

CFM

RPM

kW

1.2

CFM

RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil

For operation at 208V: Deduct approximately 0.5% from Cfm