Page 36

background image

36

R6GP-120(C/D)-235Ca

Factory Standard: 1.5Hp Horizontal Performance Chart

‡ Indicates Factory Sheave Setting for Pre-configured Units

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns

Open ‡

4

Turns
Open

4.5

Turns
Open

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

4589

4402

4304

4205

4055

3904

RPM

689

671

654

636

618

600

kW

1.52

1.39

1.29

1.19

1.10

1.02

0.2

CFM

4514

4327

4139

4021

3903

3765

3627

RPM

709

691

673

655

638

620

603

kW

1.56

1.43

1.31

1.21

1.11

1.02

0.94

0.3

CFM

4429

4299

4093

3887

3762

3636

3459

3281

RPM

727

711

693

674

657

640

623

605

kW

1.59

1.47

1.34

1.21

1.11

1.02

0.94

0.86

0.4

CFM

4184

4050

3831

3611

3471

3331

RPM

730

715

695

676

659

642

kW

1.49

1.37

1.24

1.12

1.02

0.92

0.5

CFM

4085

3924

3763

3559

3354

RPM

749

734

718

698

678

kW

1.52

1.39

1.26

1.15

1.03

0.6

CFM

3964

3822

3639

3456

3230

RPM

767

752

736

720

700

kW

1.51

1.40

1.27

1.15

1.04

0.7

CFM

3871

3686

3500

3315

RPM

785

769

754

738

kW

1.48

1.38

1.28

1.16

0.8

CFM

3849

3687

3584

3380

3175

RPM

815

801

787

772

756

kW

1.58

1.48

1.38

1.26

1.15

0.9

CFM

3580

3363

3247

RPM

817

804

791

kW

1.45

1.33

1.25

1.0

CFM

3251

RPM

821

kW

1.32

1.1

CFM

RPM

kW

1.2

CFM

RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil

For operation at 208V: Deduct approximately 0.5% from Cfm

Table 12. R6GP-120C-235Ca Series / 230V - Horizontal Configuration