Reznor R6GP Unit Installation Manual User Manual
Page 36

36
R6GP-120(C/D)-235Ca
Factory Standard: 1.5Hp Horizontal Performance Chart
‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open ‡
4
Turns
Open
4.5
Turns
Open
5
Turns
Open
5.5
Turns
Open
6
Turns
Open
0.1
CFM
4589
4402
4304
4205
4055
3904
RPM
689
671
654
636
618
600
kW
1.52
1.39
1.29
1.19
1.10
1.02
0.2
CFM
4514
4327
4139
4021
3903
3765
3627
RPM
709
691
673
655
638
620
603
kW
1.56
1.43
1.31
1.21
1.11
1.02
0.94
0.3
CFM
4429
4299
4093
3887
3762
3636
3459
3281
RPM
727
711
693
674
657
640
623
605
kW
1.59
1.47
1.34
1.21
1.11
1.02
0.94
0.86
0.4
CFM
4184
4050
3831
3611
3471
3331
RPM
730
715
695
676
659
642
kW
1.49
1.37
1.24
1.12
1.02
0.92
0.5
CFM
4085
3924
3763
3559
3354
RPM
749
734
718
698
678
kW
1.52
1.39
1.26
1.15
1.03
0.6
CFM
3964
3822
3639
3456
3230
RPM
767
752
736
720
700
kW
1.51
1.40
1.27
1.15
1.04
0.7
CFM
3871
3686
3500
3315
RPM
785
769
754
738
kW
1.48
1.38
1.28
1.16
0.8
CFM
3849
3687
3584
3380
3175
RPM
815
801
787
772
756
kW
1.58
1.48
1.38
1.26
1.15
0.9
CFM
3580
3363
3247
RPM
817
804
791
kW
1.45
1.33
1.25
1.0
CFM
3251
RPM
821
kW
1.32
1.1
CFM
RPM
kW
1.2
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
For operation at 208V: Deduct approximately 0.5% from Cfm
Table 12. R6GP-120C-235Ca Series / 230V - Horizontal Configuration