ELECTRICAL INFORMATION
Table 13. Electrical Data
Model
Number
2,3
R6GP-
Nominal
Unit
Voltage
1
High
Static
Kit #
Compressors
Outdoor
Motors
(2) ea.
Indoor
Motor
4
Inducer
Motor
Total
Unit
RLA
Unit Only
Circuit
Qty
RLA
LRA
FLA
Hp
FLA
Hp
FLA
LRA
RLA
MCA
MOP
Factory Unit Electrical Data:
-072C-(100/166)C 208 - 230 V
Factory
Std.
1 ea.
19
123
1.5
1
3.2 - 3.1
1/12
0.5
0.76
25.2
30 - 30 45 - 45
-072D-(100/166)C
460 V
1 ea.
9.7
62
0.8
1.5
12.8
16
20
-090C-200Ca
208 - 230 V
2 ea.
13.1
83.1
2.3
1.5
4.4 - 4.2
1/12
0.5
0.76
35.2
39 - 39 50 - 50
-090D-200Ca
460 V
2 ea.
6.1
41
1.2
2.1
16.7
19
20
-120C-235Ca
208 - 230 V
2 ea.
16.0
110
2.3
1.5
4.4 - 4.2
1/12
0.5
0.76
41.0
45 - 45 60 - 60
-120D-235Ca
460 V
2 ea.
7.8
52
1.2
2.1
20.1
22
25
Medium & High Static Drive Electrical Data:
-072C-(100/166)C 208 - 230 V
920609
1 ea.
19
123
1.5
1.5
4.4 - 4.2
1/12
0.5
0.76
26.4
32 - 31 50 - 45
-072D-(100/166)C
460 V
920560
1 ea.
9.7
62
0.8
2.1
13.4
16
25
-072C-166C
208 - 230 V
920613
1 ea.
19
123
1.5
2
5.9 - 5.5
1/12
0.5
0.76
27.9
33 - 33 50 - 50
-072D-166C
460 V
920618
1 ea.
9.7
62
0.8
2.8
14.1
17
25
-090C-200Ca
208 - 230 V
921481
2 ea.
13.1
83.1
2.3
2
6.0 - 5.8
1/12
0.5
0.76
36.8
40 - 40 50 - 50
-090D-200Ca
460 V
2 ea.
6.1
41
1.2
2.9
17.5
19
25
-090C-200Ca
208 - 230 V
921655
2 ea.
13.1
83.1
2.3
2
6.0 - 5.8
1/12
0.5
0.76
36.8
40 - 40 50 - 50
-090D-200Ca
460 V
2 ea.
6.1
41
1.2
2.9
17.5
19
25
-120C-235Ca
208 - 230 V
921645
2 ea.
16.0
110
2.3
2
6.0 - 5.8
1/12
0.5
0.76
42.6
47 - 47 60 - 60
-120D-235Ca
460 V
2 ea.
7.8
52
1.2
2.9
20.9
23
30
NOTES
:
1) To achieve the rated unit performance, unit voltage should be within 2% of nominal.
2) For C series units:
Nominal Unit Input Voltage = 208-230 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 187V
Maximum allowed voltage = 253V
3) For D series units:
Nominal Unit Input Voltage = 460 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 414V
Maximum allowed voltage = 506V
4) Indoor Motors meet 2010 DOE requirements (Premium Efficient)
5) Refer to High Static Drive Kit Installation Instructions for additional information
FLA = Full Load Amps; MCA = Minimum Circuit Ampacity; RLA = Rated Load Amps;
MOP = Maximum Over-Current Protection; LRA = Locked Rotor Amps