ELECTRICAL INFORMATION

Table 13. Electrical Data

Model

Number

2,3

R6GP-

Nominal

Unit

Voltage

1

High

Static

Kit #

Compressors

Outdoor

Motors

(2) ea.

Indoor

Motor

4

Inducer

Motor

Total

Unit

RLA

Unit Only

Circuit

Qty

RLA

LRA

FLA

Hp

FLA

Hp

FLA

LRA

RLA

MCA

MOP

Factory Unit Electrical Data:

-072C-(100/166)C 208 - 230 V

Factory

Std.

1 ea.

19

123

1.5

1

3.2 - 3.1

1/12

0.5

0.76

25.2

30 - 30 45 - 45

-072D-(100/166)C

460 V

1 ea.

9.7

62

0.8

1.5

12.8

16

20

-090C-200Ca

208 - 230 V

2 ea.

13.1

83.1

2.3

1.5

4.4 - 4.2

1/12

0.5

0.76

35.2

39 - 39 50 - 50

-090D-200Ca

460 V

2 ea.

6.1

41

1.2

2.1

16.7

19

20

-120C-235Ca

208 - 230 V

2 ea.

16.0

110

2.3

1.5

4.4 - 4.2

1/12

0.5

0.76

41.0

45 - 45 60 - 60

-120D-235Ca

460 V

2 ea.

7.8

52

1.2

2.1

20.1

22

25

Medium & High Static Drive Electrical Data:

-072C-(100/166)C 208 - 230 V

920609

1 ea.

19

123

1.5

1.5

4.4 - 4.2

1/12

0.5

0.76

26.4

32 - 31 50 - 45

-072D-(100/166)C

460 V

920560

1 ea.

9.7

62

0.8

2.1

13.4

16

25

-072C-166C

208 - 230 V

920613

1 ea.

19

123

1.5

2

5.9 - 5.5

1/12

0.5

0.76

27.9

33 - 33 50 - 50

-072D-166C

460 V

920618

1 ea.

9.7

62

0.8

2.8

14.1

17

25

-090C-200Ca

208 - 230 V

921481

2 ea.

13.1

83.1

2.3

2

6.0 - 5.8

1/12

0.5

0.76

36.8

40 - 40 50 - 50

-090D-200Ca

460 V

2 ea.

6.1

41

1.2

2.9

17.5

19

25

-090C-200Ca

208 - 230 V

921655

2 ea.

13.1

83.1

2.3

2

6.0 - 5.8

1/12

0.5

0.76

36.8

40 - 40 50 - 50

-090D-200Ca

460 V

2 ea.

6.1

41

1.2

2.9

17.5

19

25

-120C-235Ca

208 - 230 V

921645

2 ea.

16.0

110

2.3

2

6.0 - 5.8

1/12

0.5

0.76

42.6

47 - 47 60 - 60

-120D-235Ca

460 V

2 ea.

7.8

52

1.2

2.9

20.9

23

30

NOTES

:

1) To achieve the rated unit performance, unit voltage should be within 2% of nominal.

2) For C series units:

Nominal Unit Input Voltage = 208-230 Volt, 60 Hertz, 3 Phase

Minimum allowed unit voltage = 187V
Maximum allowed voltage = 253V

3) For D series units:

Nominal Unit Input Voltage = 460 Volt, 60 Hertz, 3 Phase

Minimum allowed unit voltage = 414V
Maximum allowed voltage = 506V

4) Indoor Motors meet 2010 DOE requirements (Premium Efficient)

5) Refer to High Static Drive Kit Installation Instructions for additional information

FLA = Full Load Amps; MCA = Minimum Circuit Ampacity; RLA = Rated Load Amps;
MOP = Maximum Over-Current Protection; LRA = Locked Rotor Amps