Table 8. R6GP-072C-166C Series - Horizontal Configuration

R6GP-072(C/D)-166C

Factory Standard: 1Hp Horizontal Performance Chart

‡ Indicates Factory Sheave Setting for Pre-configured Units

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns
Open

5

Turns

Open ‡

5.5

Turns
Open

6

Turns
Open

0.1

CFM

2914

RPM

724

kW

0.80

0.2

CFM

2703

RPM

728

kW

0.74

0.3

CFM

2771

2620

2469

RPM

778

755

731

kW

0.84

0.75

0.66

0.4

CFM

2879

2704

2529

2366

2203

RPM

833

807

781

757

732

kW

0.97

0.86

0.75

0.68

0.60

0.5

CFM

2655

2457

2259

2060

RPM

837

811

785

760

kW

0.89

0.78

0.67

0.59

0.6

CFM

2745

2569

2392

2169

1946

RPM

884

862

839

813

786

kW

1.02

0.89

0.77

0.69

0.60

0.7

CFM

2668

2474

2285

2095

RPM

912

888

865

842

kW

1.05

0.92

0.80

0.69

0.8

CFM

2572

2386

2200

1988

RPM

939

917

894

870

kW

1.07

0.93

0.79

0.70

0.9

CFM

2303

2097

RPM

942

920

kW

0.95

0.83

1.0

CFM

2254

2043

RPM

971

945

kW

0.96

0.85

1.1

CFM

RPM

kW

1.2

CFM

RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil

For operation at 208V: Deduct approximately 0.5% from Cfm