beautypg.com

Troubleshooting, Table 2. diagnostic codes for 6 - 10 ton units, Figure 11. location of unit components – Reznor R6GP Unit Installation Manual User Manual

Page 21

background image

21

If the unit does not operate properly in the cooling mode,

check the following:

• The thermostat is operating properly.

• Electrical power to the unit is turned on.

• All safety switches are closed.

• The service doors are in place.

• Transformer circuit breaker is reset.

If the unit does not operate properly in the heating mode,

check the following:

• The thermostat is operating properly.

• Electrical power to the unit is turned on.

• All safety switches are closed.

• The gas is on and shut-off valve is open.

• The service doors are in place.

• The flame roll-out control is closed.

• Refer to the diagnostic codes in Table 2 or the wiring

diagram (Figure 15, page 38).

• Transformer circuit breaker is reset.

STATUS LIGHT

(Red LED)

FAULT

CONDITION

Continuous ON

Operation Normal

2 Flashes

Pressure / centrifugal switch open with
inducer on

3 Flashes

Pressure / centrifugal switch closed with
inducer off

4 Flashes

Lockout from too many failed ignition tries

5 Flashes

Lockout from too many flame losses

6 Flashes

High temperature switch open

7 Flashes

Rollout switch open

8 Flashes

Flame present with gas off

9 Flashes

Exceeded max limit trips (5) in one call for
heat

10 Flashes

Gas valve fault

Table 2. Diagnostic Codes For 6 - 10 Ton Units

Condenser Fan

Assemblies

High/Low

Pressure Switch

Protection

Liquid Line

Filter Driers

High Efficiency

Compressors

with Crankcase

Heaters

Belt Drive

Blower Motor

Knockout

for Bottom

Power Entry**

3/4” PVC

Condensate

Drain

Permament Baserail -

No Need for Removal

with Roof Curb

Knockout for

Bottom Power

Entry

Control Wiring Entry

Power Wiring Entry

Condenser Coils

Electrical

Disconnect

Mounting

Panel +

Easy Access

Control Panel

Durable Pre-Coat

Paint

Quick Release

Filter Panel

Evaporator Coils

Exhaust Vent

Gas Line Inlet

Flame

Observation

Combustion
Air Inlet

+ Field Supplied
** Field Installed Kit Required

Figure 11. Location of Unit Components

Model R6GP-120C235C Shown

TROUBLESHOOTING