30

R6GP-072(C/D)-100C

Factory Standard: 1Hp Horizontal Performance Chart

‡ Indicates Factory Sheave Setting for Pre-configured Units

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3 Turns

Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns
Open

5

Turns

Open ‡

5.5

Turns
Open

6

Turns
Open

0.1

CFM

2999

2848

RPM

740

717

kW

0.86

0.76

0.2

CFM

2955

2785

2615

RPM

764

742

720

kW

0.88

0.79

0.69

0.3

CFM

2881

2738

2558

2377

RPM

792

766

745

723

kW

0.92

0.81

0.72

0.64

0.4

CFM

2812

2663

2514

2289

2085

RPM

821

795

769

745

727

kW

0.96

0.85

0.74

0.68

0.56

0.5

CFM

2729

2590

2426

2261

1995

1802

RPM

850

826

799

772

746

730

kW

0.97

0.85

0.77

0.68

0.60

0.46

0.6

CFM

2626

2462

2298

2026

1957

RPM

877

853

829

800

775

kW

0.99

0.87

0.76

0.64

0.58

0.7

CFM

2563

2349

2165

2018

RPM

903

879

855

833

kW

1.00

0.87

0.77

0.68

0.8

CFM

2545

2353

2100

1862

RPM

931

907

833

858

kW

1.02

0.91

0.78

0.68

0.9

CFM

2414

2306

2046

RPM

959

936

912

kW

1.04

0.92

0.79

1.0

CFM

2174

2013

RPM

964

941

kW

0.90

0.81

1.1

CFM

RPM

kW

1.2

CFM

RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil

For operation at 208V: Deduct approximately 0.5% from Cfm

Table 6. R6GP-072C-100C Series - Horizontal Configuration