Blower performance data – Reznor R6GP Unit Installation Manual User Manual
Page 28

28
BLOWER PERFORMANCE DATA
Table 4. R6GP Series Alternate Accessory Blower Drives
This equipment is outfitted with a belt driven blower assembly in order to accommodate a large variety of duct
configurations and airflow selections. The blower has been factory inspected for proper alignment, operation and
rotational direction prior to the drive motor being situated in the shipping position. The blower drive belt is located
with these instructions and must be installed by the service technician. For a more detailed explanation of belt driven
blower drives and the operation of their components please refer to any of the installation instructions listed below
for the high static drive kits.
The factory standard drive installed in these units has been set to deliver 400 Cfm/ton at an External Static Pressure
(ESP) of 0.25-0.30 in-Wg. Tables 5-10 show the full blower curves of these drive configurations and can be utilized
to easily set the adjustable motor sheave for alternate configurations. Refer to the Legend below for a description of
the table information. Once a sheave setting has been made, always inspect the blower amp draw to ensure that it
is less then the service factor amps listed on the motor. For systems that include a large number of accessories or
have very restrictive duct systems, alternate drive kits are available, refer to Table 4 below for the applicable kits. The
full blower curves for the HSD kits can be found in the applicable kit installation instructions or in the unit technical
service literature.
For units being placed into service configured for horizontal flow operation, always use the applicable NORDYNE
accessory kit for the conversion. Refer to the technical service literature for kit part numbers. These kits may require
that the over-temperature limit controls be updated for this mode of operation.
3862
1159
Indicates a recommended unit operational point
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Unit Model #
Motor
Hp
E.S.P. Range
(in-Wg)
Blower Rpm
Range (DF)
Downflow
Kit
Blower Rpm
Range (HF)
Horizontal
Kit
-072C-100C
1.5 Hp
0.7 - 1.6
916 - 1159
920609
915 - 1154
920609
-072C-166C
917 - 1186
920609
930 - 1223
920613
-072D-100C
916 - 1159
920560
915 - 1154
920560
-072D-166C
917 - 1186
920560
930 - 1223
920618
-090(C/D)-200Ca
2 Hp
0.1 - 1.9
878 - 1208
921481
928 - 1227
921655
-120(C/D)-235Ca
2 Hp
0.1 - 1.4
651 - 916
921645
653 - 917
921645
NOTE:
Refer to R6GP TSL or Accessory Kit Installation Instructions for actual blower charts.