BLOWER PERFORMANCE DATA

Table 4. R6GP Series Alternate Accessory Blower Drives

This equipment is outfitted with a belt driven blower assembly in order to accommodate a large variety of duct
configurations and airflow selections. The blower has been factory inspected for proper alignment, operation and
rotational direction prior to the drive motor being situated in the shipping position. The blower drive belt is located
with these instructions and must be installed by the service technician. For a more detailed explanation of belt driven
blower drives and the operation of their components please refer to any of the installation instructions listed below
for the high static drive kits.

The factory standard drive installed in these units has been set to deliver 400 Cfm/ton at an External Static Pressure
(ESP) of 0.25-0.30 in-Wg. Tables 5-10 show the full blower curves of these drive configurations and can be utilized
to easily set the adjustable motor sheave for alternate configurations. Refer to the Legend below for a description of
the table information. Once a sheave setting has been made, always inspect the blower amp draw to ensure that it
is less then the service factor amps listed on the motor. For systems that include a large number of accessories or
have very restrictive duct systems, alternate drive kits are available, refer to Table 4 below for the applicable kits. The
full blower curves for the HSD kits can be found in the applicable kit installation instructions or in the unit technical
service literature.

For units being placed into service configured for horizontal flow operation, always use the applicable NORDYNE

accessory kit for the conversion. Refer to the technical service literature for kit part numbers. These kits may require
that the over-temperature limit controls be updated for this mode of operation.

3862

1159

Indicates a recommended unit operational point

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Unit Model #

Motor

Hp

E.S.P. Range

(in-Wg)

Blower Rpm

Range (DF)

Downflow

Kit

Blower Rpm

Range (HF)

Horizontal

Kit

-072C-100C

1.5 Hp

0.7 - 1.6

916 - 1159

920609

915 - 1154

920609

-072C-166C

917 - 1186

920609

930 - 1223

920613

-072D-100C

916 - 1159

920560

915 - 1154

920560

-072D-166C

917 - 1186

920560

930 - 1223

920618

-090(C/D)-200Ca

2 Hp

0.1 - 1.9

878 - 1208

921481

928 - 1227

921655

-120(C/D)-235Ca

2 Hp

0.1 - 1.4

651 - 916

921645

653 - 917

921645

NOTE:

Refer to R6GP TSL or Accessory Kit Installation Instructions for actual blower charts.