LAARS Heating Systems

222

Unconfigured Outlet high limit

setpoint setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

223

Unconfigured Stack limit setpoint

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

224

Invalid DHW (Domestic Hot

Water) demand source setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

225

Invalid Flame threshold setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

226

Invalid Outlet high limit setpoint

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

227

Invalid DHW (Domestic Hot

Water) high limit setpoint setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

228

Invalid Stack limit setpoint setting L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

229

Invalid Modulation output setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

230

Invalid CH (Central Heat)

demand source setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

231

Invalid Delta T limit delay setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

232

Invalid Pressure sensor type

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

234

Invalid Outlet high limit enable

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

235

Invalid Outlet connector type

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

236

Invalid Inlet connector type

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

Code Description

L or H Procedure