3 - venting and combustion air, 1 combustion air, Boilers and water heaters – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual
Page 13: Page 9, Herm, Table 4 - required combustion air pipe material, Table 3a - pvc vent terminal kits
Page 9
N
eo
T
herm
Boilers and Water heaters
Method 1: Two permanent openings, one commencing within
12” (300mm) of the top and one commencing within 12”
(300mm) of the bottom, of the enclosure shall be provided.
The openings shall communicate directly, or by ducts, with
the outdoors or spaces that freely communicate with the
outdoors. When directly communicating with the outdoors, or
when communicating to the outdoors through vertical ducts,
each opening shall have a minimum free area of 1 square inch
per 4000 Btu/hr (550 square mm/kW) of total input rating
of all equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening shall
have a minimum free area of not less than 1 square inch per
2000 Btu/hr (1100 square mm/kW) of total input rating of all
equipment in the enclosure.
Method 2: One permanent opening, commencing within
12” (300mm) of the top of the enclosure, shall be permitted.
The opening shall directly communicate with the outdoors
or shall communicate through a vertical or horizontal duct
to the outdoors or spaces that directly communicate with the
outdoors and shall have a minimum free area of 1 square inch
per 3000 Btu/hr (734 square mm/kW) of the total input rating
of all equipment located in the enclosure. This opening must
not be less than the sum of the areas of all vent connectors in
the confined space.
Section 3 -
VENTING AND COMBUSTION AIR
3.1 Combustion Air
NeoTherm boilers and water heaters must have provisions
for combustion and ventilation air in accordance with the
applicable requirements for Combustion Air Supply and
Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in
Canada, the Natural Gas and Propane Installation Code, CSA
B149.1. All applicable provisions of local building codes must
also be adhered to.
A NeoTherm unit can take combustion air from the space
in which it is installed, or the combustion air can be ducted
directly to the unit. Ventilation air must be provided in either
case.
Combustion Air From Room
In the United States, the most common requirements specify
that the space shall communicate with the outdoors in
accordance with method 1 or 2, which follow. Where ducts
are used, they shall be of the same cross-sectional area as the
free area of the openings to which they connect.
INSTALLATION STANDARDS
MATERIAL
UNITED STATES
CANADA
ABS
ANSI/ASTM D1527
PVC, sch 40
ANSI/ASTM D1785 or D2665
Air pipe material must be chosen
CPVC, sch 40
ANSI/ASTM F441
based upon the intended application of the boiler.
Single wall galv. steel
26 gauge
Table 4 - Required Combustion Air Pipe Material
PRO TECH (FasNSeal)
HEAT FAB (Saf-T-Vent)
Z FLEX (Z-Vent)
SIZE
Boiler
Flue
Intake Air
Boiler
Intermediate
Flue
Intake Air
Boiler
Flue
Intake Air
Adapter Termination
Termination Adapter Adapter Termination
Termination Adapter Termination
Termination
399-600
F303759
FSBS4
FSAIH04
KB285600 9454BUREZ-1* 9492 9414TERM 2SVSLA04 2SVSTP04 2SVSTEX0490
FSRC4(R.C)
303888
5400CI
2SVSRCX04
750-850
F303759 FSBS6 FSAIH04
303888
Table 3b - Approved Stainless Terminations and Adapters
HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS
2” PVC
3” PVC
4” PVC
6” PVC
Size
S
tandar
d
C
onc
ent
ri
c
C
A
0060
00
F
lus
h M
ount
C
A
0101
00
S
tandar
d
C
A
0059
00
C
onc
ent
ri
c
239
-44069
-01
F
lus
h M
ount
C
A
0101
01
S
tandar
d
F
lus
h M
ount
C
A
0101
02
S
tandar
d
80
incl.
opt.
opt.
opt.
opt.
opt.
n/a
n/a
n/a
105
incl.
opt.
opt.
opt.
opt.
opt.l
n/a
n/a
n/a
150
n/a
n/a
n/a
incl.
opt.
opt.
n/a
n/a
n/a
199/210
n/a
n/a
n/a
incl.
opt.
opt.
n/a
n/a
n/a
285
n/a
n/a
n/a
opt.
opt.
opt.
incl.
opt.
n/a
399
n/a
n/a
n/a
n/a
n/a
n/a
incl.
opt.
n/a
500
n/a
n/a
n/a
n/a
n/a
n/a
incl.
opt.
n/a
600
n/a
n/a
n/a
n/a
n/a
n/a
incl.
opt.
opt.
750
n/a
n/a
n/a
n/a
n/a
n/a
n/a
opt.
incl.
850
n/a
n/a
n/a
n/a
n/a
n/a
n/a
opt.
incl.
Concentric vent terminal = 10 ft. pipe length
Table 3a - PVC Vent Terminal Kits