N
eo
T
herm
Boilers and Water heaters
108
Flame lost in run
L
1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector, flame detector
siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the
module.
109
Ignition failed
L
1. Check the main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector, flame detector
siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the
module.
110
Ignition failure occurred
H
Hold time of recycle and hold option. Will not be a lockout fault. Hold
only. Internal hardware test. Not a lockout.
111
Flame current lower than weak
threshold
H
Hold time of recycle and hold option. Will not be a lockout fault. Hold
only. Internal hardware test. Not a lockout.
113
Flame circuit timeout
L
Flame sensed during initiate or off cycle. Produces a Hold for 240
seconds. If still present after 240 seconds, system will lockout.
122
Lightoff rate proving failed
L
1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
123
Purge rate proving failed
L
1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
128
Fan speed failed during prepurge H or L 1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change
speeds.
3. Change the VFD
4. If the fault persists, replace the module.
129
Fan speed failed during
preignition
H or L 1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change
speeds.
3. Change the VFD
4. If the fault persists, replace the module.
130
Fan speed failed during ignition
H or L 1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change
speeds.
3. Change the VFD
4. If the fault persists, replace the module.
131
Fan movement detected during
standby
H
1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change
speeds.
3. Change the VFD
4. If the fault persists, replace the module.
Code Description
L or H Procedure