beautypg.com

Dhw piping, one heater, two vertical tanks, Laars heating systems – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 32

background image

Page 28

LAARS Heating Systems

Figure 23 - DHW Piping, One Heater, Two Vertical Tanks

NOTES:

1. Optional CWMU & Recirc. line location.

2. Locate NTV DHW sensor or remote aquastat well

in lower 1/3 of tank.

3. Back flow preventer may be required - check local codes.

4. Thermal expansion tank may be required - check local codes.

5. Factory mounted pumps are sized for a max pipe length of

30’ total, 6-90° elbows, full pipe size.

6.

Caution: Pump sizing must be based on water

hardness at job site.

WARNING: This drawing shows

suggested piping configuration and

valving. Check with local codes and

ordinances for additional requirements.

This manual is related to the following products: